13.6.4
Error messages displayed in pop-up windows
All the messages that appear on the display in a pop-up window are described below.
Error message
Description
Notes
Local Bus
Local Bus error
See par. 13.7
Contact wear
Contact wear prealarm
Contact wear
≥
80%
L prealarm
Protection L prealarm
T prealarm
Protection T prealarm
Warning Iw
Iw threshold exceeded
Timing L
Timing protection L
Timing S
Timing protection S
Timing S2
Timing protection S2
Timing G
Timing protection G
Timing U
Timing protection U
Timing UV
Timing protection UV
Timing OV
Timing protection OV
Timing RP
Timing protection RP
Error message
Description
Password error
Session impossible
A programming session cannot be started due to a contingency (e.g. a timer-controlled delay still elapsing)
Value outside range
Value beyond the established limits
Failed 1001/2001
Incongruence between thresholds of protections L and S (SET1/SET2)
Failed 1002/2002
Incongruence between thresholds of protections I and S (SET1/SET2)
Failed 1003/2003
Incongruence between thresholds of protections L and S2 (SET1/SET2)
Failed 1004/2004
Incongruence between thresholds of protections I and S2 (SET1/SET2)
Failed 3001
Inconsistency as to language change
Exception 6
Control temporarily unavailable
Unavailable
Function temporarily unavailable
Invalid date
Date has not been set
Parameters revised
Programming session concluded correctly
Cancelled
Programming session cancelled
Failed
Programming session rejected
13.7 Troubleshooting PR123/DC unit
The following table lists a series of typical service conditions, to help you understand and solve hypothetical faults or malfunctions.
Note:
1.
Before consulting the following table, check for any error messages appearing for some seconds on the display.
2.
FN indicates the normal operation of the PR123/DC.
3.
In the case where the suggestions proposed do not lead to a solution of the problem, please contact the ABB SACE assistance service.
N o .
Situation
Possible causes
Suggestions
1
The trip test cannot be run
1. The busbar current is > 0
1. FN
2. The TC is not connected
2. Check the messages on the display
2
Trip times lower than expected
1. Threshold too low
1. Correct threshold
2. Curve too low
2. Correct curve
3. Thermal memory enabled
3. Exclude if not necessary
4. The SdZ is inserted
4. Exclude if not necessary
3
Trip times higher than expected
1. Threshold too high
1. Correct threshold
2. Curve too high
2. Correct curve
3. Curve I
2
t inserted
3. Exclude if not necessary
4 Rapid trip, with I3=Off
Iinst tripped
FN with short-circuit with high I
5 High earth I, but no trip happens
Function G prevented with I>4In
FN
6
Display off
1. Faulty voltage sockets connection 1. Warning, see 13.3.4
2. Vaux missing and the voltage
2. FN, see 13.2.2
is below the minimum value.
3. Temperature out of range
3. FN, see 13.2.9.8