13.5.6 Test Menu
Access to the Test menu is password protected.
The menu shows the state of the CB, in the dialog module (COM module) the state of the springs and the position of the CB, and in this submenu
you can make the CB open or close. Using the "Trip Test" function lets you view the disabling/enabling of the Trip. If it is enabled, the circuit-breaker
is opened. The function is only available with a busbar current of nil (use Vaux, PR030/B or PR010/T).
On the page only with Vaux, you can also see the state of the circuit-breaker "STATUS", and thus make sure that the input is correctly wired.
The surfing path is summarized in the following table:
13.5.6.1
Test Menu table
Parameter / Function
Values
Notes
CB status
Open/Closed/Indefinite
Indefinite in case of fault only
Auto Test
Display test
Trip Test
Enabled/Disabled
PR120/D-M
State of springs
Loaded/Unloaded
Module
Position of CB
Isolated/Withdrawn
Open CB
Close CB
PR120/K
Input
ON
Module
Auto Test
- - -
Zone
Protection S
selectivity
(status)
Input
ON/OFF
Force Output
Release Output
Protection G
(status) Input
ON/OFF
Force Output
Release Output
13.5.7 Information Menu
The Information Menu enables you to view the data relating to the protection unit and the type of circuit-breaker.
1/3
Protection Unit
Nr. :
Version
Normative
Software
G0000A03A
: LSIG
: IEC
: P 1.00
Device
: PR123/DC
1/3
Circuit Breaker
Device
Nr. :
Rated Curr.
Installation
Maintenance
: E2B800/SP
: 800 A
: June 12, 2007
: June 12, 2007
AF 050 94 092
1/2
Protection Unit
Circuit Breaker
Protection Unit
About
Enter
↵
ESC +
↓
+ Enter
↵
13.5.7.1
Information on the trip and opening data
The PR123/DC unit saves all the information relating to the type of protection tripped, the opening data, the date and time. Using the "i Test" key
makes the release show all these data directly on the display. There is no need for an auxiliary power supply for this function. With an auxiliary
power supply, the information is shown immediately on the display without the need to press the "i Test" key and remains displayed indefinitely
until you press the key.
The information remains available for 48 hours with dead relay. The data relating to the last 20 trips are stored in the unit's memory. By connecting
a PR030/B battery unit and PR010/T or a BT030 wireless communication unit, you can retrieve the information relating to the last 20 trips recorded.
Access to view the opening data is via the Historicals submenu in the Measurements menu. The following is an example of the information provided:
Again in the Measurements menu, you can view the percentage of contact wear, which is an indication of the electrical life of the electrical contacts
in the circuit-breaker.
In any case, functionality of the relay is in no way modified by the presence of the wear messages.
The prealarm message (wear > 80%, "warning" LED lighting up) indicates that the wear has reached a high value. The alarm message (100%
wear, "alarm" LED lighting up) indicates that it is necessary to check the state of contact wear.
The percentage of wear depends on the number of openings carried out by the circuit-breaker and by the absolute current interrupted during
each of them.
1/3
Last Trip
June
2007
12,
I1:
625A
L Protection
N.02
8:52:11:733
Number of openings due to the protections and to the TRIP tests.
Indication for protection tripped.
- Value of the current interrupted if the LSIU has tripped.
- Value of the current G if G has tripped.
- Value of the voltage if OV, UV have tripped.
- Value of the current and power if the Rp has tripped.
4/5
Device test
Settings
Test
Measures
Menu
Password
Enter password
0***
1/6
CB open
Auto Test
Trip Test (disabled)
CB status
Test
Enter
↵
Enter
↵