L3447
Emax DC
28/108
L3728
Doc. No.
Model
Apparatus
Scale
Page No.
1SDH000635R0002
11. Protection releases - General notes
The Emax series of ABB air circuit-breakers now has a new range of electronic releases for DC applications called PR122/DC and PR123/DC.
The new protection releases integrate all the functions of their predecessors, adding new and interesting technical features that are useful for
satisfying every current and future system installation need.
Every operational requirement is now met thanks to the different performance levels of the new relays and of the additional modules that can
be fitted inside them (PR120/V, PR120/LV, PR120/K, PR120/D-M, PR120/D-BT).
A table can best illustrate the technical features and the mix and matchability of the relays.
Key:
S
: standard function/unit,
O
: optional function/unit,
-
: function/unit unavailable.
Notes:
1.
: with internal PR120/D-BT module
2.
: PR120/V or PR120/LV for standard (see section 14.1)
Function/Unit
PR122/DC
PR123/DC
Current protections
(L, S, I)
S
S
Current protections G
-
S
Additional protections
(U)
-
S
Voltage protections
(UV, OV, RP)
-
S
Other protections
(S2)
-
S
Temperature protection
(OT)
S
S
MCR protection
S
S
Thermal memory
S
S
Local bus for separate auxiliary units
S
S
Wire communication
(RS485)
S
(1)
S
(1)
Data Logger
S
S
Compatibility with SD.Pocket
S
S
Compatibility with SD.Testbus
S
S
Compatibility with PR010/T
S
S
Dual setting
-
S
PR120/V Measuring
(internal voltages module)
S
(2)
S
(2)
PR120/LV Measuring
(internal voltages module)
S
(2)
S
(2)
PR120/K Signalling
(internal signalling module)
O
O
PR120/D-M Com
(internal communication module)
O
O
PR120/DC
(override protection module)
S
S
PR021/K
(separate signalling unit)
O
O
HMI030
(separate graphics interface)
O
O
PR030/B
(separate power supply unit)
S
S
BT030
(separate Bluetooth communication unit)
O
O