80
4.
LATset
- Leaving air temperature
setpoint. Range = 35°F-80°F, and the
default is 50°F.
5.
OATset
- Outside air temperature
setpoint. Range = 35°F-60°F, and the
default is 35°F.
6.
LLTset
- “Low Limit Time” temperature
setpoint. Range = 35°F-50°F, and the
default is 35°F. If ‘LLTSet’ temperature
is not reached within ‘BelowLLT’ time
after reaching full output, the status relay
will operate.
7.
RESETset
-
“Reset Setpoint”
temperature. Range = 35°F-80°F, and the
default is 50°F.
8.
ManSTG -
Temporary manual override a
specified stage testing, 0=normal
operation, 1-6 to override corresponding
stages. Range = 0-6, and the default is 0.
The manual override may be used for unit
testing of each stage. Stage 1 will be at
50% to test SCR and stages 2-6 will be
full capacity. A manual override will
expire in ten minutes if not manually
cancelled by resetting ‘ManSTG’ back to
zero.
LED Flash Alarm Codes
The flashing red LED will be to the right of
the screen. The number of blinks is described
below. The LCD screen will also display the
screens.
1
= LATA probe open/short
2
= LATB probe open/short
3
= OAT sensor open/short
4
= Leaving air temp over limit
5
= Cooling down after hi limit’ event
6
= LAT below low limit
7
= Stage 1 only recovery after mechanical
limit
8
= Shutdown after too many hi limit events
Содержание RQ NextGen Series
Страница 2: ......
Страница 26: ...26 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations...
Страница 40: ...40 Figure 23 Post Corner Hole Piping Figure 24 Post Back Hole Piping...
Страница 86: ...86 Figure 35 Example 2 6 ton through the Base Gas Piping Note RQ units will only contain one Heat Exchanger...
Страница 88: ...88 Gas Heater Operating Instructions Figure 36 Gas Heater Instructions...
Страница 95: ...95...
Страница 96: ...96...
Страница 105: ...105 Maintenance Log E Coated Coil...
Страница 107: ...107...