79
6.
LLTset
- “Low Limit Time” temperature
(°F) setpoint. If this temperature is not
reached at full output, relay will pull in.
7.
Stage
- Current operating stage 1-6.
8.
Stage
- Current operating stage 1-6.
MOD
- Modulation rate % being applied
to stage one heat strip SCR.
9.
OAT
- Outside air inlet temperature (°F).
10.
LATA
-
Leaving air probe "A"
temperature (°F).
11.
LATB
-
Leaving air probe "B"
temperature (°F).
12.
ManSTG -
Manual override stage for
system testing. Any override
automatically cancels after ten minutes; 0
indicates normal operation, 1-6
corresponds to stages 1-6 being forced
on. Stage 1, the SCR, is forced to 50%.
System Setting Screens
These screens are access by pressing the up
button and then entering the technician
password
2425
. The screens are scrolled
through by pressing either right or left
buttons on the controller. Adjustment is made
by pressing the up and down buttons. After a
short time of inactivity, the screen will go
back to the Status Display Screens.
1.
StartDly -
Seconds of delay after the
'Enable' call before heating starts. This is
to allow the Supply Fan to come up to
speed. Supply Fan VFD’s have a 45
second ramp up time. Range = 1sec-
60sec, and the default is 15sec.
2.
BelowLLT
- "Below Low Limit Time".
Range = 10sec-1800sec, and the default
is 10sec. If ‘LLTset’ temperature is not
reached within ‘BelowLLT’ after
reaching full output, the status relay will
operate.
3.
Stages
- Number of stages. Range = 1-6,
and the default is 1. The number of stages
can be determined using Table 25.
Table 27 - Stages of Electric Preheat
Tonnages
Feature 14B
Stages
RQ 2-6 tons
G = 10 kW
1
H = 15 kW
J = 20 kW
Содержание RQ NextGen Series
Страница 2: ......
Страница 26: ...26 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations...
Страница 40: ...40 Figure 23 Post Corner Hole Piping Figure 24 Post Back Hole Piping...
Страница 86: ...86 Figure 35 Example 2 6 ton through the Base Gas Piping Note RQ units will only contain one Heat Exchanger...
Страница 88: ...88 Gas Heater Operating Instructions Figure 36 Gas Heater Instructions...
Страница 95: ...95...
Страница 96: ...96...
Страница 105: ...105 Maintenance Log E Coated Coil...
Страница 107: ...107...