64
Disconnect the wiring from the motor and
loosen the bolt that clamps the motor mount
to the motor. Remove the motor and fan
through the top of the orifice.
Figure 32 - Removal of a Condenser Fan
Assembly
Reinstallation
Set the motor back into the motor mount and
tighten bolt. Adjust fan until the top of the
blade is even with the top of the orifice.
Reconnect wires, then attach the fan grill at
all the points where screws were removed.
Refrigerant-to-Water Heat Exchanger
Condenser water pump, condenser water
piping, cooling tower or geothermal loop,
pressure gauges, strainers, piping insulation
and all components of the waterside piping
must be field installed.
Water-Source Heat Pump Applications
Water-source heat pump units using 100%
outside air must have electric preheat if the
application has a potential for operation with
air entering the indoor coil below 6.1°C
(43°F) with a water loop temperature of
21.1°C (70°F).
Open Loop Applications
This product contains one or more
refrigerant-to-water heat exchangers made of
copper, which is subject to corrosion and
failure when exposed to chlorides.
Do not allow water containing any form of
chlorides to enter this heat exchanger.
Common forms of chlorides include:
1. Sea water mist entering an open cooling
tower system.
2. Contaminated make-up water containing
salt water.
3. Disinfecting the water loop with solutions
containing sodium hypochlorite.
Chlorides will result in a premature failure of
the condenser.
WATER-SOURCE HEAT
PUMP APPLICATIONS
Water-source heat pump units using
100% outside air must have electric
preheat if the application has a
potential for heat pump heating
operation with air entering the indoor
coil below 6.1°C (43°F) with an
entering water loop temperature of
21.1°C (70°F).
CAUTION
OPEN LOOP APPLICATIONS
Failure of the condenser as a result of
chemical corrosion is excluded from
coverage under AAON Inc. warranties
and the heat exchanger
manufacturer’s warranties.
WARNING
Содержание RQ NextGen Series
Страница 2: ......
Страница 26: ...26 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations...
Страница 40: ...40 Figure 23 Post Corner Hole Piping Figure 24 Post Back Hole Piping...
Страница 86: ...86 Figure 35 Example 2 6 ton through the Base Gas Piping Note RQ units will only contain one Heat Exchanger...
Страница 88: ...88 Gas Heater Operating Instructions Figure 36 Gas Heater Instructions...
Страница 95: ...95...
Страница 96: ...96...
Страница 105: ...105 Maintenance Log E Coated Coil...
Страница 107: ...107...