22
General Information
RQ Series packaged rooftop units, heat
pumps and outdoor air handling units have
been designed for outdoor installation only.
Units are assembled, wired, charged and run
tested at the factory.
Startup and service must be performed by a
Factory Trained Service Technician.
Certification of Gas Heat Models
a.
AAON gas heat exchangers have
successfully completed 10,000 burner
operation cycles and corrosion resistance
as specified per test standard ANSI 21.47.
All gas heat exchangers used in AAON
appliances are certified for use
downstream of evaporator or cooling
coils.
b.
Certified as a Category III forced air
furnace with or without cooling.
c.
Certified for outdoor installation only.
d.
Certified for installation on a combustible
roof with a minimum of 30.5 cm (12”)
high curb.
Certification of Steam or Hot Water Heat
Models
a.
Certified as a forced air heating system
with or without cooling.
b.
Certified for outdoor installation only.
c.
Certified for installation on a combustible
roof with a minimum of 30.5 cm (12”)
high curb.
Certification of Electric Heat Models
a.
Certified as an electric warm air furnace
with or without cooling.
b.
Certified for outdoor installation only.
c.
Certified for installation on a combustible
roof with a minimum of 30.5 cm (12”)
high curb.
Certification of Cooling Models
a.
Certified as a commercial central air
conditioner with or without electrically
operated compressors.
b.
Certified for outdoor installation only.
c.
Certified for installation on a combustible
roof with a minimum of 30.5 cm (12”)
high curb.
d.
Certified with refrigerant R-410A coils or
with chilled water cooling coils.
Codes and Ordinances
RQ Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995 5
th
Edition/CSA C22.2
No. 236, ANSI, UL-60335-2-40 4
th
Edition,
Safety Standard Z21.47b-2008/CSA 2.3b-
2008, and ANSI Safety Standard Z83.8-
2006/CSA 2.6-2006.
Improper installation, adjustment,
alteration, service or maintenance can
cause property damage, personal
injury or loss of life. Startup and
service must be performed by a
Factory Trained Service Technician. A
copy of this IOM must be kept with the
unit.
WARNING
These units must not be used for
heating or cooling at any time during
any phase of construction. Very low
return air temperatures, harmful
vapors, and misplacement of the
filters will damage the unit and its
efficiency.
CAUTION
Содержание RQ NextGen Series
Страница 2: ......
Страница 26: ...26 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations...
Страница 40: ...40 Figure 23 Post Corner Hole Piping Figure 24 Post Back Hole Piping...
Страница 86: ...86 Figure 35 Example 2 6 ton through the Base Gas Piping Note RQ units will only contain one Heat Exchanger...
Страница 88: ...88 Gas Heater Operating Instructions Figure 36 Gas Heater Instructions...
Страница 95: ...95...
Страница 96: ...96...
Страница 105: ...105 Maintenance Log E Coated Coil...
Страница 107: ...107...