![AAON RQ NextGen Series Скачать руководство пользователя страница 73](http://html2.mh-extra.com/html/aaon/rq-nextgen-series/rq-nextgen-series_installation-operation-and-maintenance_5032934073.webp)
73
WARNING: Monolithic wheels with internal
bearings must not be soaked to avoid
corroding bearing.
(Note: some staining of the desiccant may
remain and is not harmful to performance).
Before removing, rapidly run finger across
surface of segment to separate polymer strips
for better cleaning action. Rinse dirty
solution from segment and remove excess
water before reinstalling in wheel.
Air Seals
Four adjustable diameter seals are provided
on each cassette to minimize transfer of air
between the counter flowing airstreams.
To adjust diameter seals, loosen diameter seal
adjusting screws and back seals away from
wheel surface. Rotate wheel clockwise until
two opposing spokes are hidden behind the
bearing support beam. Using a folded piece
of paper as a feeler gauge, position paper
between the wheel surface and diameter
seals.
Adjust seals towards wheel surface until a
slight friction on the feeler gauge (paper) is
detected when gauge is moved along the
length of the spoke. Retighten adjusting
screws and recheck clearance with “feeler”
gauge.
Diameter Seal Adjustment
Wheel Drive Components
The wheel drive motor bearings are pre-
lubricated and no further lubrication is
necessary.
The wheel drive pulley is secured to the drive
motor shaft by a combination of either a key
or D slot and set screw.
The set screw is secured with removable
locktite to prevent loosening. Annually
confirm set screw is secure. The wheel drive
belt is a urethane stretch belt designed to
provide constant tension through the life of
the belt. No adjustment is required. Inspect
the drive belt annually for proper tracking
and tension. A properly tensioned belt will
turn the wheel immediately after power is
applied with no visible slippage during start-
up.
Installation Considerations
Energy recovery cassettes are incorporated
within the design of packaged units,
packaged air handlers and energy recovery
ventilators. In each case, it is recommended
that the following considerations be
addressed:
Do not use acid based cleaners,
aromatic solvents, steam or
temperatures in excess of 76.7
°
C
(170°F)damage to the wheel may
occur!
CAUTION
Содержание RQ NextGen Series
Страница 2: ......
Страница 26: ...26 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations...
Страница 40: ...40 Figure 23 Post Corner Hole Piping Figure 24 Post Back Hole Piping...
Страница 86: ...86 Figure 35 Example 2 6 ton through the Base Gas Piping Note RQ units will only contain one Heat Exchanger...
Страница 88: ...88 Gas Heater Operating Instructions Figure 36 Gas Heater Instructions...
Страница 95: ...95...
Страница 96: ...96...
Страница 105: ...105 Maintenance Log E Coated Coil...
Страница 107: ...107...