Output Current Specifications
Model
Continuous Current (A)
Overload Current
5
ZENER 8000-V030
30
45
ZENER 8000-V044
44
66
ZENER 8000-V058
58
87
ZENER 8000-V066
66
99
ZENER 8000-V084
84
126
ZENER 8000-V100
100
150
ZENER 8000-V132
132
198
ZENER 8000-V168
168
252
ZENER 8000-V200
200
300
ZENER 8000-V300
300
450
ZENER 8000-V400
400
600
Troubleshooting guide
Symptom
Cause
Remedy
Front Display does not illuminate.
Input power wiring not connected
properly.
Input voltage not within
specification.
Check input power wiring, refer to
the ZENER 8000-V Electrical
Installation Diagram. Measure the
input voltage at the power input
terminals. Check with
specifications.
Motor does not rotate when UP
button on the Console is pressed.
Enable signal is not active.
Check that the EN terminal is
connected to +5V. Check that the
ENABLED message is displayed.
ZENER 8000-V is in REMOTE
Check that if you have a remote
terminal it is not at +5V with
respect to COM.
Speed is set to minimum
Increase speed by holding down
the UP button.
Motor does not rotate when
remote START signal is activated.
Incorrect control signal wiring.
Check control wiring to terminals
and the terminal functions
assigned. Refer to Control Wiring
Diagrams and Terminal
Configurations.
Enable signal is not active.
Check that the EN terminal is
connected to +5V. Check that the
ENABLED message is displayed.
ZENER 8000-V is in LOCAL
Check that your remote terminal is
at +5V with respect to DIG COM
A direction has not been selected.
Check that either a FWD or a REV
terminal has been assigned and
that it is at +5V with respect to DIG
5
60 second rating