ZENER 8000-V Installation Manual
IM00165
37
Standard Industrial Terminals
Typical Connections
This section shows the typical configurations applicable to a wide range of industrial applications. The motor
speed may be controlled from the local console on the ZENER 8000-V or a remote signal source. Switching
between local and remote operation is controlled by a contact closure. This terminal configuration is the factory
default. Several alternative arrangements for starting and stopping are shown.
O No Power
O Power On and
Stopped
C Power On and
Drive running
RL1 - Run
No Power O
Power On and O
not tripped
Power On,
Drive tripped C
RL2 - Trip
+5V
1
D1
2
D2
3
D3
4
D4
5
EN
6
COM
7
SCN
8
Vref
9
IN+
10
IN-
11
A
12
15
16
18
17
RL1
RL2
Control Board Terminals
RS-485 / EIA-485
Serial Communications
B
13
C
14
+
-
8
9
10
11
Input reference source
Run
Stop/
Reset
Local
Remote
Optional
Optional Output Disable
1k to 10k Ohm
potentiometer
Single Direction 2-Wire Control
1
2
3
4
5
6
Power-up start up
1
2
3
4
5
6
Start
Stop/
Reset
Local
Remote
Optional
Single Direction 3-Wire Control
Optional Output Disable
Local / Remote
In “local”, control is
from the front panel
console. In “remote”,
control from the
terminal strip
Optional Wiring
If selection between local
and remote is not
required, place a link
between terminals 1 and
5. If the output disable is
not required place link
between terminals 1 and 6
i
The functions of terminals D1…4 are
programmable. In the default
configuration, the following functions are
assigned to the terminals:
I07 RESET
D1
I02
~STOP
D2
I00
FWD & LATCH
D3
I11
REMOTE
D4