ZENER 8000-V Installation Manual
IM00165
43
Pressure Ctl-00
user menu
Reqd Pressure
500.0 kPa
Reqd Pressure
500.0 kPa
Pressure Units
kPa
Rated Motor Amps
40.0 A
Overload Amps
40.0 A
Min frequency
30 Hz
Pressure scale
1000.0 kPa
To change the required pressure:
Press the
ESC
push button on the console to reveal
the
application menu.
Press
ENTER
to view the first application parameter.
Press
UP
or
DOWN
to view other parameters.
Press
ENTER
again to edit the displayed parameter.
o
Press
UP
or
DOWN
to adjust the value,
ENTER
to accept the value or
ESC
to abandon changes
Application Parameters
This screen displays the preset pressure reference
required for the pump.
This screen displays the minimum output frequency
setting of operation.
This screen allows for the selection of pressure units for
display.
This screen allows for the full scale of pressure to be
entered. The full scale is used for live displays
This screen displays the value of the motor’s name plate
current. Note the default value is model size dependent
This screen displays the value of the overload current
setting for the motor. Note the default value is model
size dependent.