ZENER 8000-V Installation Manual
IM00165
3
Installation
ZENER 8000-V mounting location
The ZENER 8000-V chassis is intended to be mounted in a switchboard style enclosure with the heatsink section
protruding through the rear wall of the enclosure. The input and output line reactors provided as part of the
ZENER 8000-V should be mounted within the switchboard, adjacent to, or on the enclosure floor, below the
ZENER 8000-V module chassis. The control console is separate to the ZENER 8000-V chassis and intended to be
mounted on the front of the switchboard enclosure for convenient operation. Mechanical protection may be
required to prevent damage to the heatsink section in some environments. The ZENER 8000-V portion within
the user’s switchboard enclosure is designed for use in a pollution degree 2
1
environment. The system
integrator and user are responsible for providing and maintaining this environment inside the switchboard
enclosure under all circumstances for the lifetime of the equipment.
Installation Information
CAUTION
The ZENER 8000-V must be mounted in a vibration free situation with heatsink fins
protruding through the wall of a switchboard type enclosure.
Do not mount the ZENER 8000-V where it is subject to heating by direct sunlight or
other heat radiating sources.
ZENER 8000-V must be mounted vertically. No other mounting orientation is
acceptable.
The thermal design of the user’s switchboard enclosure must be accommodate the
total heat dissipation of the ZENER 8000-V components together with the heat
dissipation any other equipment in the same enclosure and maintain the internal
ambient temperature within the range of 0 - 50°C without condensation.
Attention is drawn to the potential for condensation in vulnerable environments.
Additional precautions may be required for all enclosure types.
All of the parts associated with a drive system using parallel modules must be
installed in the same enclosure.
The installation location and environment should provide for safe access and
working conditions for maintenance personnel.
The mechanical design of the enclosure should provide for the safe removal and
replacement of drive modules and line reactors for maintenance purposes in a way
that suits the circumstances of the final installation site.
Do not drill holes in the ZENER 8000-V module enclosure except in the gland
plates.
Remove the module gland plate before drilling cable holes.
Do not allow metal shavings or any other conductive material to enter the
ZENER 8000-V module enclosure or line reactors. Serious damage may result.
1
Any pollution present is non-conductive