ZENER 8000-V Installation Manual
_
40
IM00165
STEP 4. Follow the instructions on page 27 for ZENER 8000-V start up, setting the parameters according to the
table below. Alternative values may be used to suit the application.
Menu
Menu Item
Suggested Setting
G00 INPUT/OUTPUT
G01 Inpt fxn CFG
(Input terminal
configuration)
I00 FWD & LATCH = D3(4)
(default)
I02 ~STOP = D2(3) (default)
I07 RESET = D1(2) (default)
I11 REMOTE = D4(5) (default)
G00 INPUT/OUTPUT
G03 RL1
G030 RL1 Signal = RUN (default)
G04 Rl2
G040 RL2 Signal = TRIP (default)
B00 MOTOR
B01 MOTOR VOLTS
Motor nameplate voltage
B02 MOTOR AMPS
Motor nameplate amps
B03 MOTOR HZ
Motor nameplate frequency
B04 MOTOR RPM
Motor nameplate RPM
D00 PROTECTION
D01 CURRENT LIM M
Motor nameplate c10%
D02 I2t Thermal overload
Motor nameplate current
E00 STOP/START
E03 AUTO RESTART
E030 ARs ALLOWED = 5
E04 Reset by PF
ENABLED
F00 REFERENCES
F01 REMOTE REF
AI(10,11) or PRESET or CONSOLE
as selected in Step 3
C00 PERFORMANCE
C03 RAMP
C030 ACCEL TIME = 10 sec
C031 DECEL TIME = 10 sec
End of procedure