ZENER 8000-V Installation Manual
IM00165
15
Control console
1
2
3
Connectors
ZENER.8000
MASTER
Module 1
Terminator
25
25
25
Cat-5
cable
**
*
*
*
*
Control console connector not fitted on slave units
**
Connector 2 on master not used (cover fitted)
Important
Use only control cables supplied to interconnect inverters. Do not use substitute
cables (eg computer cables) - electrical noise problems may occur
1,2 or 3 slave units may be used
1
2
3
Connectors
ZENER.8000
SLAVE
Module 4
1
2
3
Connectors
ZENER.8000
SLAVE
Module 3
1
2
3
Connectors
ZENER.8000
SLAVE
Module 2
All control wiring
and
communications
connects to
master module
only
Control Cable Diagram
(Module viewed from below)
Control Connector Identification
Connector 3
RJ-45 for
Cat-5 cable
Connector 1
(25 pin female)
Connector 2
(25 pin male)
Control Interconnection for Parallel Units
A direct earth bonding wire of not less than 6mm
2
is required between adjacent inverter
modules for functional purposes.
In addition, one (only one!) earth connection should be made from the master inverter module to
the switchboard earth link. Do not use the inverter module earth connections to earth other
components or cable screens etc. The reason for this requirement is to avoid possible earth
currents from other sources flowing in the earth bonding wire between inverter modules. High
frequency currents in the bonding connections may induce sufficient voltage between inverter
modules to cause improper operation.