ZENER 8000-V Installation Manual
IM00165
47
Fault Message
Description
T2 OVER TEMP
The temperature of sensor T2 has risen beyond the protection rating of the ZENER 8000-V
T3 OVER TEMP
The temperature of sensor T3 has risen beyond the protection rating of the ZENER 8000-V
T4 OVER TEMP
The temperature of sensor T4 has risen beyond the protection rating of the ZENER 8000-V
T5 OVER TEMP
The temperature of sensor T5 has risen beyond the protection rating of the ZENER 8000-V
T6 OVER TEMP
The temperature of sensor T6 has risen beyond the protection rating of the ZENER 8000-V
T7 OVER TEMP
The temperature of sensor T7 has risen beyond the protection rating of the ZENER 8000-V
T8 OVER TEMP
The temperature of sensor T8 has risen beyond the protection rating of the ZENER 8000-V
MODULE 1
Parallel inverter trip detected in inverter module No. 1 (paralleled inverter systems only).
MODULE 2
Parallel inverter trip detected in inverter module No. 2 (paralleled inverter systems only).
MODULE 3
Parallel inverter trip detected in inverter module No. 3(paralleled inverter systems only).
MODULE 4
Parallel inverter trip detected in inverter module No. 4 (paralleled inverter systems only).
Status Messages
The prevailing operating conditions are indicated with a status message on the bottom right of the console
display. The status messages include:
Status Message
Description
U MODE 1
Remote user mode 1 message. Refer to
F0122 MODE1 text
for message customisation.
U MODE 2
Remote user mode 2 message. Refer to
F0132 MODE2 text
for message customisation.
-<UW1>-
User defined warning message. Refer to
G272 Warning txt
for message customisation.
-<UW2>-
User defined warning message. Refer to
G282 Warning txt
for message customisation.
-<UW3>-
User defined warning message. Refer to
G292 Warning txt
for message customisation.
-<UW4>-
User defined warning message. Refer to
G302 Warning txt
for message customisation.
V LIMIT
The motor is regenerating or the input voltage is too high
C LIMIT
The motor is drawing its maximum overload current
P LIMIT
The motor's absorbed power exceeds the ZENER 8000-V rating when operating from a single phase
supply
ESO FWD
The ZENER 8000-V is operating in Essential Services Override mode with forward rotation
ESO REV
The ZENER 8000-V is operating in Essential Services Override mode with reverse rotation
OFF LINE
The ZENER 8000-V has not been given a terminal strip run command in line contactor mode
NO AC
The ZENER 8000-V has been given a terminal strip run command in line contactor mode but has
detected no AC input voltage supply
CHARGING
The ZENER 8000-V is waiting for the DC bus capacitors to be fully charged before running the motor
NOT EN
The ZENER 8000-V is on but has no enable signal so it is unable to turn a motor
IDLE REM
The ZENER 8000-V is idle in remote mode