STEP 3. Choose your speed reference and connect it as shown.
Speed control from an external potentiometer
This is typically used for simple manual speed
control. See also Console Reference below.
Speed control from an external signal
Go to the F00 REFERENCES menu and select
F01 REMOTE REF. Press Enter. Use the arrows
to display the options. Press Enter when
AI(10,11) is displayed. Press ESC
Go to the G00 INPUT/OUTPUT menu and select
G02 AI(10,11). Set G028 for the type of input
signal (0-10V, 0-5V, 4-20mA or Custom).
See the Reference Manual for more
information.
Preset speed
This provides a single fixed speed.
Go to the F00 REFERENCES menu and select F01
REMOTE REF. Press Enter. Use the arrows to
display the options. Press Enter when F100 PRESET
1 is displayed. Press Enter again. Now set your
desired preset speed. Press Enter. No speed
reference wiring is necessary.
Console reference
This uses the Up and Down arrows on the front
panel to control the speed.
Go to the F00 REFERENCES menu and select F01
REMOTE REF. Press Enter. Use the arrows to
display the options. Press Enter when CONSOLE is
displayed. No speed reference wiring is necessary