3-30
SM-16005-rev.2
TROUBLESHOOTING
CN201
(To Fan Motor)
LED1
PCN201
(To TB1)
< Checking for Fan Motor >
Remove the connector of the fan motor and measure the resistance value between each of the pins (twice).
Check whether the resistance value is over or not according to the Decision Basis shown below. When
performing the second measuring, make sure to change the tester (Red/ Black).
1st Measurement
2nd Measurement
Decision Basis
Tester
Resistance
Value
Tester
Resistance
Value
Resistance values of both
1st and 2nd measurings
are over 10
W
Red
Black
W
Red
Black
W
PG
GND
GND
PG
Vsp
GND
GND
Vsp
Vcc
GND
GND
Vcc
Vm
GND
GND
Vm
2 PG (Blue)
3 Vsp (Yellow)
4 Vcc (White)
5 GND (Black)
8 Vm (Red)
Connector for Fan Motor
● Ducted (Medium Static) with EconoFresh Kit
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...