SM-16005-rev.2
3-45
TROUBLESHOOTING
3.4.1 Test Run Using Wired Controller
(1) Wired Controller (CIW01)
Back
Test Run Setting: 2 units
MODE
:
COOL
SPEED
:
AUTO
ON
Rtrn
Sel.
Adj.
Back to (1) after checking
Wired Controller
Indication
No Indication
* The power supply is not turned ON.
* The connection of the controller cable
is incorrect.
* The connecting wires of power supply
line are incorrect or loose.
1. Connection between Connector and Wires
2. Connecting Points of Controller Cable
3. Contact of Connectors of Controller Cable
6. RSW Setting on Indoor Unit Printed Circuit Board
7. Wire Connecting Order of Bridge Cable
8. Connecting Points of Bridge Cable
9. Contact of Connectors of Bridge Cable
* The electrical wiring between indoor unit
and outdoor unit is disconnected, or the
power supply is not turned ON.
* The setting of unit number is incorrect.
* The connection of control cables
between each indoor unit are incorrect.
(When one wired controller controls
multiple units.)
Number of
connected units
is incorrect.
Fault
Inspection Points after the Power Supply OFF
4. Connection Order of each Terminal Block
5. Screw Fastening of each Terminal Block
Normal
Abnormal
Move to (4) on the next page.
(3) Checking Procedure for Abnormalities
If no indication or "00" appears, or the number of the units indicated is less than the actual
number of the units, there is an abnormality.
If "TEST RUN" and the total number of the units connected
to the wired controller (for example "2 units") are indicated
on the wired controller, the connection of the controller cable
is correct.
* The total number of indoor units connected is indicated
on the liquid crystal display (LCD).
* If the indicated number is not equal to the actual number of connected indoor units,
the auto-address function is not performed correctly due to incorrect wiring, or
electromagnetic interference. Turn OFF the power supply, and correct the wiring after
checking the following points (Do not repeat turning ON and OFF within 10 seconds.)
(a) The power supply for the indoor unit is NOT turned ON or the incorrect wiring.
(b) Loose connection between Indoor Units or Wired Controller.
(c) Incorrect Setting of Indoor Unit Address (The indoor unit address is duplicated.)
(1) Turn ON the power supply of the indoor and outdoor units.
(2) Set the TEST RUN mode with the wired controller.
Press and hold the "Menu" and the "Back/Help" buttons
simultaneously for more than three seconds.
Select “Test Run” by pressing “ ” and press “OK”.
The Test Run screen is displayed.
NOTE:
For other controllers,
refer to the “Installation Manual” for each controller.
NOTE:
When “00 unit” is indicated,
the auto-address function
may be performing.
Cancel “Test Run” mode
and set it again.
OK
Menu
Back/Help ECO
On/Off
Menu
Button
Back/Help
Button
On/Off
Button
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...