3-22
SM-16005-rev.2
TROUBLESHOOTING
Correctly connect wires.
Check continuity
and looseness of
connection screws.
Check terminal Nos.
Incorrect Wiring
Disconnected Wire
Contact Failure
Incorrect Wiring
Replace or repair
wires, or tighten screws.
O.U. PCB: Outdoor Unit PCB
I.U. PCB: Indoor Unit PCB
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
(Outdoor Unit and
Change-Over Box)
Blown Fuse for
Power Supply
or Activation of
Breaker
Check for breakage
of insulation.
Short Circuit between Wires
Measure insulation
resistance.
Short Circuit to Ground
Measure voltage with
tester.
Supply power.
Power Failure or No Power Supply
Measure resistance
between wires and
insulation resistance.
Faulty Comp. Motor
Measure resistance
between wires and
insulation resistance.
Replace outdoor unit
fan motor and fuse.
Replace O.U. PCB
if faulty.
Faulty Outdoor Unit
Fan Motor
Blown Fuse
on PCB
(Outdoor Unit)
Check for breakage
of wire insulation.
Remove cause of
short circuit and
replace fuse.
Short Circuit between Wires
Measure insulation
resistance.
Remove cause of
short circuit and
replace fuse.
Short Circuit to Ground
Disconnected
Wires,
Contact Failure or
Incorrect
Connection
Check continuity of
wires.
Check for looseness
of connection screws.
Check terminal Nos.
Replace and repair
wires, tighten screws
or correct wires.
Between Outdoor Unit
and Indoor Unit
Power Supply Wiring
for Outdoor Unit
Measure resistance
of coil.
Replace magnetic
switch (CMC) and fuse.
Faulty Solenoid Coil for
Magnetic Switch (CMC)
for Comp. Motor
Measure resistance
between wires and
insulation resistance.
Replace fan motor
and fuse.
Faulty Outdoor Unit
Fan Motor
Correctly connect wires.
Replace it if faulty.
PCB Failure
(Outdoor Unit,
Indoor Unit)
Check connection.
Disconnected Wires to
I.U./O.U. PCB
Faulty I.U./O.U.PCB
Remove cause of
short circuit.
Replace fuse and/or
I.U./O.U. PCB if faulty.
Remove cause of
short circuit to ground.
Replace fuse and/or
I.U./O.U. PCB if faulty.
Replace comp. and
fuse. (O.U.) Replace
inverter PCB and/or
PCB if faulty. (O.U.)
Correctly connect wires.
Measure O.U. PCB
output. *2)
Replace O.U. PCB.
Incorrect Power Supply Circuit of O.U. PCB
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...