SM-16005-rev.2
3-47
TROUBLESHOOTING
3.4.2 Checking the Test Run
(1) Indoor and Outdoor Fan
Check that the indoor fan and outdoor fan rotate correctly and the airflow is smooth.
(2) Power Supply Voltage
Check the power supply.
If the power supply is abnormal, contact the electric
power company.
Usually, voltage drop will occur when starting the
operation as shown in the figure (V
2
).
In order to protect the device, comply with the following
normal range of the power supply voltage.
<Normal Range of Power Supply Voltage>
• Supply Voltage: Rated Voltage < +10%
Operating Voltage (V
3
): Rated Voltage < +10%
• Starting Voltage (V
2
): Rated Voltage > -15%
Voltage Imbalance between Phase: < 3%
(3) Normal Operating Pressure
Normal operating suction pressure is 29 to 159.5 psi (0.2 to 1.1 MPa) and normal operating discharge
pressure is 145 to 507.6 psi (1.0 to 3.5 MPa) when the refrigerant charge quantity is correct. Check
the operation pressure in the test run mode.
(4) High Pressure Switch
Check the operation pressure of the high pressure switch in the table below.
(b) When the high pressure retry control is activated, alarm code “
” is indicated on the 7-segment
display of the outdoor unit PCB. If the high pressure retry control occurs three times or more within
30 minutes, alarm code “
” is indicated on the LCD of the wired controller or the 7-segment display
of the outdoor unit PCB.
(5) High Pressure Increase Retry (Protection Control)
(a) High pressure will increase when one of the following procedures is performed.
Refrigerant
Operation Pressure
R410A
601 psi (4.15MPa)
Initial Voltage
< Voltage Change >
(V
1
)
Starting Voltage
(V
2
)
Operating Voltage
(V
3
)
Cover the air inlet of outdoor unit
during cooling operation.
Cover the air inlet of indoor unit
during heating operation.
NOTE:
High pressure may not increase until the high pressure switch is activated because of the
temperature condition.
For CIW01
Sel.
OP MODE
I.U.
: RCI-3.0FSN3
MODEL : F .02
Alarm Code:
22
O.U.
: RAS-3HVRNM2
01-02
AlarmRst
Address
Entr
IDU
: ******
ODU : ******
Chek
OK
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...