SM-16005-rev.2
3-21
TROUBLESHOOTING
O.U. PCB: Outdoor Unit PCB
I.U. PCB: Indoor Unit PCB
(
)
Is LED3 (yellow)
on I.U. PCB ON?
Is LED3 (yellow) on
I.U. PCB flashing more
than once in 10 seconds.
Yes
Yes
Faulty O.U. PCB.
Set it correctly.
Faulty I.U. PCB.
Faulty I.U. PCB.
Check wiring between
outdoor unit and indoor
units or fuse (EF) for
I.U./O.U. PCB.
No
Yes
No
Does Alarm occur with
all indoor units?
Yes
No
Check other indoor units.
No
No
Is LED3 (yellow)
ON even if connector
CN2 on I.U. PCB
is removed?
Yes
Yes
Indoor
Unit
Does refrigerant system
No. setting between
O.U. and I.U correspond?
O.U.: DSW4 and RSW1
I.U.: DSW5 and RSW2
Is LED1 (red) on
Change-Over Box
PCB ON?
Is LED3 (green) on
Change-Over Box
PCB ON?
Yes
No
No
Check Change-Over
Box wiring.
Check wiring between
outdoor unit and indoor
units.
No
Is LED2 (yellow) on
Change-Over Box PCB
flashing more than
once in 10 seconds?
No
Replace fuse.
Check other
Change-Over Boxes.
Yes
Is the fuse for
Change-Over Box
PCB blown?
Yes
Is voltage between
"L1" and "N" of PCN1
on Change-Over Box
PCB 208 or 230V?
Faulty Change-Over
Box PCB.
No
Change-Over
Box
(In Case
of Heat
Recovery
System)
Yes
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...