5-18
SM-16005-rev.2
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
27
Cd
Not Prepared
-
-
Not Used (Use as 00 conditions)
28
CE
Not Prepared
-
-
Not Used (Use as 00 conditions)
29
CF Change of Louver Swing Angle
○
00
01
02
Standard (7-Step Operation)
Cold Draft Prevention
(5 Steps: lower 2 steps cut off)
High Ceiling (higher 2 steps cut off)
30
d1
Power Supply ON/OFF 1
○
00
01
Not Available
Available
31
d2
Not Prepared
-
-
Not Used
32
d3
Power Supply ON/OFF 2
○
00
01
Not Available
Available
33
d4
Prevention for Cooling Discharge Air
Temperature Decrease
○
00
01
Not Available
Available
34
d5
Prevention for Heating Discharge Air
Temperature Decrease
○
00
01
Not Available
Available
35
d6
Not Prepared
-
-
Not Used (Use as 00 conditions)
36
d7
Damper Minimum Opening (*9)
○
00
6
o
01
12
o
02
18
o
03
24
o
04
30
o
05
36
o
06
42
o
07
48
o
37
E1
All Fresh Operation (*10)
○
00
01, 02
Not Available
Available
38
E2
Enthalpy Sensor
○
00
01
Not Available
Available
39
E3 Not Prepared
-
-
Not Used (Use as 00 conditions)
40
E4
CO
2
Gas Sensor
○
00
01, 02
Not Available
Available
41
E5 Not Prepared
-
-
Not Used (Use as 00 conditions)
42
E6
Indoor Fan Operation Time After
Cooling Operation Stoppage
○
00
01
02
Not Available
60 min.
120 min.
43
E7 Not Prepared
-
-
Not Used (Use as 00 conditions)
44
E8
Fan Operation Control during
Heating Thermo-OFF
○
00
01
Not Available (LOW)
SLOW
45
E9 Not Prepared
-
-
Not Used (Use as 00 conditions)
46
EA Not Prepared
-
-
Not Used (Use as 00 conditions)
47
Eb Fan Operation Control during
Cooling Thermo-OFF
○
00
01
02
Not Available
LOW
SLOW
48
EC Forced Thermo-ON Stoppage during
Cooling
○
00
01
Not Available
Available
49
Ed Not Prepared
-
-
Not Used (Use as 00 conditions)
50
EE Not Prepared
-
-
Not Used (Use as 00 conditions)
51
EF
Automatic Fan Speed Control
(High 2)
○
00
01
Not Available
Available
52
F0 Not Prepared
-
-
Not Used
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...