SM-16005-rev.2
5-39
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(2) Rotation Control Function
The rotation control switches multiple indoor unit operating mode to FAN mode (Thermo-OFF) in order
one by one.
Fan
Operation*
1
Fan
Operation*
1
Fan
Operation*
1
Cooling Operation
Cooling Operation
Cooling
Operation
Cooling
Operation
Time
Indoor Unit 1
Indoor Unit 2
Indoor Unit 3
Order of Fan
Operation
1
Order of Fan
Operation
2
Order of Fan
Operation
In3
The indoor unit fan
operation is
performed in rotation by
indoor unit address Nos.
NOTES:
1. The fan mode time can be selected in the interval of three minutes, five minutes and ten minutes.
2. It is possible to change the rotation assigned number according to the minimum differential between
the setting temperature and indoor temperature.
(3) Intermittent Control Function
The intermittent control repeats Cooling/Heating and Fan (Thermo-OFF) mode in fixed intervals.
30 Minutes
30 Minutes
Cooling Operation
20 Minutes
Cooling Operation
20 Minutes
Fan Operation
10 Minutes
Fan Operation
10 Minutes
Cooling Operation
17 Minutes
Cooling Operation
17 Minutes
Fan Operation
13 Minutes
Fan Operation
13 Minutes
Cooling Operation
15 Minutes
Cooling Operation
15 Minutes
Fan Operation
15 Minutes
Fan Operation
15 Minutes
Time
SAV: LOW
SAV: MED
SAV: HIGH
NOTE:
The fan mode is repeated in the interval of five minutes (SAV: LOW), ten minutes (SAV: MED) and fifteen
minutes (SAV: HIGH) during heating operation.
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...