![background image](http://html1.mh-extra.com/html/york/idm030b21e-series/idm030b21e-series_service-manual_4036600125.webp)
SM-16005-rev.2
5-37
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(132) Not Prepared (r4)
(133) Not Prepared (r5)
(134) Not Prepared (r6)
(135) Not Prepared (r7)
(136) Not Prepared (r8)
(137) Not Prepared (r9)
(138) Not Prepared (rA)
(139) Not Prepared (rb)
(140) Not Prepared (S1)
(141) Not Prepared (S2)
(142) Not Prepared (S3)
(143) Not Prepared (S4)
(144) Not Prepared (S5)
(145) Not Prepared (S6)
(146) Not Prepared (S7)
(147) Not Prepared (S8)
(131) Setback Temperature Compensation (During card key removal, setpoint is setbacked) (r3)
This function is utilized to change the indoor temperature condition to Thermo-ON/OFF.
In case the setback operation is enabled and the card key is removed, setpoint is compensated and
fan operate at “LOW” speed.
NOTES:
● This function is not available for all fresh mode and gas sensor mode.
● Depending on the operation range the compressor may stop and this unit switches to fan mode
during heating or cooling operation.
● Function (36) "Damper Minimum Opening (d7)" should be set to "00" for this function. Higher step
may increase the load and affect the air outlet temperature of other standard indoor units.
By default,
Cooling: Se4
o
F
(+2.5
o
C
)
Heating: Setpoint -4
o
F
(-2.5
o
C
)
When the external signal is detected (card key is inserted), return to the original setting temperature.
Setting Condition
Actual Control Temperature
00 (Standard)
Wired Controller Setting Temperature (Indicated Value) +4
o
F (2.5
o
C)
01
Wired Controller Setting Temperature (Indicated Value) +5
o
F (3.0
o
C)
02
Wired Controller Setting Temperature (Indicated Value) +6
o
F (3.5
o
C)
03
Wired Controller Setting Temperature (Indicated Value) +7
o
F (4.0
o
C)
04
Wired Controller Setting Temperature (Indicated Value) +8
o
F (4.5
o
C)
05
Wired Controller Setting Temperature (Indicated Value) +9
o
F (5.0
o
C)
06
Wired Controller Setting Temperature (Indicated Value) +10
o
F (5.5
o
C)
07
Wired Controller Setting Temperature (Indicated Value) +1
o
F (0.5
o
C)
08
Wired Controller Setting Temperature (Indicated Value) +2
o
F (1.0
o
C)
09
Wired Controller Setting Temperature (Indicated Value) +3
o
F (1.5
o
C)
10
Wired Controller Setting Temperature (Indicated Value) +3
o
F (2.0
o
C)
Compensation for setback operation can be changed as shown in the table below.
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...