SM-16005-rev.2
3-13
TROUBLESHOOTING
03: Backlight Test
04: Contrast Test
05: Run Indicator Test
A
(1) Press and hold “Menu” and “ECO” simultaneously
for three seconds during the normal mode (when
unit is not operating).
The Check Menu is displayed.
Check Menu
Self Checking
02
/
02
I. U./O. U. PCB Check
Entr
Sel.
Rtrn
Back
OK
(2) Select “Self Checking” from the Check Menu and
press “OK”.
(3) Select the process for “Self Checking”.
* To start self check, press “ECO”.
* To clear EEPROM, press “ ” and “ECO”
simultaneously.
See EEPROM clear process (15) below.
0 1 : 0 0 0
P-3400
ARF-8Y050
2008.11.06 12:34
Self Checking
(4) LCD Test
Press “OK” and the screen changes as shown at
the right.
0 2 : 0 0 0
Self Checking
(5) Backlight Test
LCD brightness is changed gradually by pressing
“OK”.
0 3 : 0 0 0
Self Checking
(6) Contrast Test
Contrast of the LCD gradually changes by
pressing “OK”.
(7) Run Indicator Test
Press “OK” and the run indicator flashes in red
and green twice for each.
(8) Button Input Test
Press the nine buttons one-by-one. The number
indicated with “
A
” counts up as buttons are
being pressed.
* The order of pressing buttons is random.
Do not press more than one button at a time.
They are not counted.
0 6 : 0 0 0
Self Checking
(4) Self-Checking
Self-Checking checks the wired controller and clears EEPROM (storage cell inside of the wired
controller).
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...