3-24
SM-16005-rev.2
TROUBLESHOOTING
Alarm
Code
Abnormality of Thermistor for Indoor Unit Inlet Air Temperature
(Inlet Air Thermistor)
NOTE:
This figure is applicable to the following thermistors.
1. Inlet Air Thermistor (THM1), 2. Liquid Pipe Thermistor (Freeze Protection) (THM3), 3. Gas Pipe Thermistor (THM5),
4. Outlet Air Thermistor (THM2), 5. Outside Air Thermistor or Remote Thermistor (THM4)
l
The RUN indicator (red) flashes.
l
The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code*
1)
,
the model name*
1)
and the number of connected indoor units are displayed on the LCD. The indoor unit
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
*1) Except for some models.
H
This alarm code is displayed when a short circuit (0.24kΩ or less) or disconnection (840kΩ or more) of
the thermistor is detected during a heating or cooling operation. The operation automatically restarts
when the malfunction is removed.
Yes
Yes
Connect them.
No
Failure of
Thermistor
Failure of I.U. PCB
No
Is thermistor THM1
(for inlet air temp.)
connected to THM1
of I.U. PCB?
Is resistance of THM1
between 0.24k
Ω
and
840k
Ω
?
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Failure of
Inlet Air
Thermistor
Check resistance.
Replace thermistor
if faulty.
Failure
Check connection.
Correctly connect wires.
Incorrect Connection
Replace I.U. PCB
and check operation.
Replace I.U. PCB
if faulty.
Failure of I.U. PCB
0
10
20
30
40
50
60
70
80
(-15) (-10) (-5) (0) (5) (10) (15) (20) (25) (30) (35) (40) (45) (50) (55) (60)
82
61
46
35
27
20.5
16
12.5
10
8
5.3
3.6
2.5
90
Thermistor
Resistance
(kΩ)
5
14 23 32 41 50 59 68 77 86 95 104 113 122 131 140
Ambient Temperature (
o
F(
o
C))
Indication on Outdoor Unit PCB
(Alarm Code 11 ~ 19)
Unit No. of
Malfunctioning Indoor Unit
Alarm Code
(11 ~ 19)
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...