SM-16005-rev.2
3-37
TROUBLESHOOTING
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Measure superheat.
Correctly charge
refrigerant after
repairing gas leakage.
Measure and check
field-supplied pipes.
Use correct pipes.
Excessively
Low Suction
Pressure
Gas Leakage
or Shortage
of Refrigerant
Insufficient
Cooling
Operation
Excessively
Small
Diameter
Tube or
Long Piping
Check whether or not
temp. difference exists
before/after check valve.
Replace check valve
for outdoor unit.
Incorrect
Activation of
Check Valve
of Outdoor
Unit
Check temp. difference.
Remove clogging.
Clogging at
Low Pressure
Piping
“Motion Sensor is
activated” is indicated
on Wired Controller
It is normal.
Activation of
Motion Sensor Control
Insufficient
Airflow to
Indoor Unit
Heat
Exchanger
Check temp. difference
at inlet and outlet of
strainer.
Replace strainer in
indoor unit.
Clogged
Strainer in
Indoor Unit
Clogging at
Low Pressure
Piping
Check for any clogging.
Remove clogging.
Check connection
cord and connector.
Replace connector.
Check for clogged
air filter.
Clean air filter.
Check for obstacle at
inlet or outlet.
Remove obstacles.
Excessively
Low Air
Temp. to
Indoor Unit
Heat
Exchanger
Insufficient revolution
of indoor unit fan motor?
Replace fan motor.
Check short-circuited
indoor unit air.
Remove cause of
short-circuited.
Is there operation
sound from coil?
Replace coil.
Is thermistor on
compressor normal?
Replace thermistor.
Is thermistor
installed correctly on
compressor?
Correctly install it.
Failure or
Malfunction
of Electronic
Expansion
Valve
Calculate heat load.
Use a larger unit.
Indoor Heat Load is Larger
than Cooling Capacity
Abnormalities of Devices
Other
Abnormalities
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...