5-26
SM-16005-rev.2
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(22) Thermistor of Wired Controller (C8)
This function is utilized to control the unit by the built-in thermistor of the wired controller (wired
controller thermistor) instead of the inlet air thermistor.
Set this function at “01” or “02” when utilizing this function.
However, even if this function is set at “01” or “02”, if the detecting temperature is abnormal due to the
failure of the thermistor of the wired controller, etc., the control is changed to the inlet air thermistor of
the indoor unit automatically.
(30) Power Supply ON/OFF 1 (Automatic Operation when Power Supply Is ON) (d1)
This function is utilized to run/stop the unit by turning ON/OFF the power supply.
When this function is utilized in the condition that there is no person to operate the unit, monitor the
system for potential unit failure.
NOTE:
The unit is stopped even when the power supply is turned ON/OFF due to power failure. If power
failure occurs during the stoppage of the unit, the operation is restarted after the power supply is
restored.
(31) Not Prepared (d2)
(26) Not Prepared (CC)
(27) Not Prepared (Cd)
(28) Not Prepared (CE)
Do not change this function when using this unit. When it is used, the function of outdoor air intake may not work
effectively.
(29) Change of Louver Swing Angle (CF)
This function is utilized to the change louver swing angle.
Setting
Condition
Louver Swing Angle
(Air Discharge Angle)
Purpose
00
7 Steps
Standard Operation
01
Lower 2 Steps are Cut
Draft Prevention
02
Higher 2 Steps are Cut
For High Ceiling
NOTE:
When changing the setting, turn OFF the power supply or
allow the louver to make one complete swing fully in the auto
swing mode to validate the setting.
Setting
Condition
Logic of
Contact
Sequence
Activation
00
A Contact
Normal
Forced
Stoppage
01
B Contact
Normal
Forced
Stoppage
Contact "Close"
Contact "Open"
Indoor
PCB
Indoor
PCB
Air
Discharge
Angle
(23) Not Prepared (C9)
(24) Not Prepared (CA)
(25) Selection of Forced Stoppage Logic (Cb)
This function is utilized to select the logic of the contact for forced stoppage signal input.
The setting condition and the logic of the contact are as shown below.
Selected Thermistor
Setting
Controlled Indoor Temp.
Thermistor of Wired Controller
00
Indoor Suction Thermistor
01
Thermistor of Wired Controller
02
Average Value of Indoor Suction Thermistor and
Thermistor of Wired Controller
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...