SM-16005-rev.2
4-3
MAINTENANCE
TURN OFF all POWER supply switches.
(2) There are two PCBs, control PCB (PCB1) and power PCB (PCB2). Both PCBs are secured with four
PCB holders. Clamp the center of the PCB holders using a long-nose plier to pull out the PCB.
Phillips Screwdriver, Long-nose Pliers
Tool
NOTE:
Do not touch any components on the PCB.
Do not apply excessive force to the PCB or it will cause a malfunction.
4.2.1 Removing PCB
(1) Loosen two M4 screws securing the electrical box cover and remove the electrical box cover by lifting
it up.
Phillips Screwdriver
Tool
Electrical Box Cover
Screws
CAUTION
UTILISER DES FILS
D
ALIMEN
TAT
ION EN CUIVRE.
'
ATTENTION
USE COPPER SUPPL
Y
WIRES.
87
0
9
4 3
6 5
1
32
RSW1
RSW2
98
1
0
5 4
7 6
2
6
5
5 6
DSW5
ON
1
4
2 3
1 2
ON
3 4
DSW6
CN
8
HA
CN
7
CN17
CN11
CN14
THM4
THU1
CN3
THM5
THM2
THM1
THM3
CN19
CN1
PCN7
PCN6
CN2
2
DSW7
1
ON
1 2
4
DSW4
3
ON
DSW
3
DSW
9
TP
DSW8
2 3
1
ON
ON
1 2
ON
1
6
5
3 4
2
CN28
CN3
3
AB
12
R/L1
S/L2
MP/N
CN201
PCN201
PCN202
CN203
CN202
PCB2
Connector for Fan Motor
PCB1
Connector for Thermistor
Connector for Float Switch
Connector for Expansion Valve
Connector for EconoFresh Kit
Connector for Condensate Pump
NOTE:
During the removal or installation of the parts if the insulation material attached on the cabinet is removed,
then reapply and repair the insulation. Otherwise, condensation may occur when cold air enters.
4.2 Maintenance of Indoor Unit
Use the specified non-flammable refrigerant (R410A) to the outdoor unit in the refrigerant cycle.
Do not charge the unit with materials other than R410A, such as hydrocarbon refrigerants
(propane, etc.), oxygen, flammable gases (acetylene, etc.) or poisonous gases when installing,
maintaining and moving the unit. Contamination of these are extremely dangerous and may
cause an explosion, fire, and injury.
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...