5-32
SM-16005-rev.2
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(64) Cooling Lower Limit for Setting Temperature (FC)
This function is utilized to limit the lowest setting temperature for FAN/COOL/DRY operations.
When this function is valid, it provides the appropriate cooling operation and energy saving.
The setting conditions and the minimum setting temperature for cooling are as follows:
<Example>
(65) Heating Upper Limit for Setting Temperature (Fd)
This function is utilized to limit the highest setting temperature for HEAT operation.
When this function is valid, it provides the appropriate heating operation and energy saving.
The setting conditions and the heating upper limit for the setting temperature are as follows:
<Example>
Setting Condition
Details
Minimum Setting Temperature
(FAN/COOL/DRY) *
00
Standard Value
66
o
F (19
o
C)
01
Lower Limit +2
o
F (Lower Limit +1
o
C)
68
o
F (20
o
C)
02
Lower Limit +4
o
F (Lower Limit +2
o
C)
70
o
F (21
o
C)
03
Lower Limit +6
o
F (Lower Limit +3
o
C)
72
o
F (22
o
C)
04
Lower Limit +8
o
F (Lower Limit +4
o
C)
74
o
F (23
o
C)
05
Lower Limit +10
o
F (Lower Limit +5
o
C)
76
o
F (24
o
C)
06
Lower Limit +11
o
F (Lower Limit +6
o
C)
77
o
F (25
o
C)
07
Lower Limit +12
o
F (Lower Limit +7
o
C)
78
o
F (26
o
C)
08
Lower Limit +14
o
F (Lower Limit +8
o
C)
80
o
F (27
o
C)
09
Lower Limit +16
o
F (Lower Limit +9
o
C)
82
o
F (28
o
C)
10
Lower Limit +18
o
F (Lower Limit +10
o
C)
84
o
F (29
o
C)
* In case of Standard Unit
Setting Condition
Details
Setting Temperature Upper Limit
(HEAT) *
00
Standard Value
86
o
F (30
o
C)
01
Upper Limit -2
o
F (Upper Limit -1
o
C)
84
o
F (29
o
C)
02
Upper Limit -4
o
F (Upper Limit -2
o
C)
82
o
F (28
o
C)
03
Upper Limit -6
o
F (Upper Limit -3
o
C)
80
o
F (27
o
C)
04
Upper Limit -8
o
F (Upper Limit -4
o
C)
78
o
F (26
o
C)
05
Upper Limit -9
o
F (Upper Limit -5
o
C)
77
o
F (25
o
C)
06
Upper Limit -10
o
F (Upper Limit -6
o
C)
76
o
F (24
o
C)
07
Upper Limit -12
o
F (Upper Limit -7
o
C)
74
o
F (23
o
C)
08
Upper Limit -14
o
F (Upper Limit -8
o
C)
72
o
F (22
o
C)
09
Upper Limit -16
o
F (Upper Limit -9
o
C)
70
o
F (21
o
C)
10
Upper Limit -18
o
F (Upper Limit -10
o
C)
68
o
F (20
o
C)
11
Upper Limit -20
o
F (Upper Limit -11
o
C)
66
o
F (19
o
C)
12
Upper Limit -22
o
F (Upper Limit -12
o
C)
64
o
F (18
o
C)
* In case of Standard Unit
Factory-Setting: "00"
(Lower Limit 66+0=66
o
F (19+0=19
o
C))
Setting Condition: "06"
(Lower Limit 66+11=77
o
F (19+6=25
o
C))
66
o
F
(19
o
C)
86
o
F
(30
o
C)
86
o
F
(30
o
C)
77
o
F
(25
o
C)
Temperature Setting: Available
Setting Temperature at Wired Controller
Temperature Setting
: Not Available
Temperature Setting
: Available
Factory-Setting: "00"
(Upper Limit 86-0=86
o
F (30-0=30
o
C))
Setting Condition: "09"
(Upper Limit 86-16=70
o
F (30-9=21
o
C))
64
o
F
(18
o
C)
86
o
F
(30
o
C)
64
o
F
(18
o
C)
70
o
F
(21
o
C)
Setting Temperature at Wired Controller
Temperature Setting: Available
Temperature Setting
: Not Available
Temperature Setting
: Available
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...