SM-16005-rev.2
3-19
TROUBLESHOOTING
*1): Refer to Section 3.1.4 (3) above for details.
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Activation of
Float Switch
Failure of
Float Switch
Failure of
Condensate
Pump
Contact Failure
Incorrect Connection
Failure
Contact Failure
Incorrect Connection
Failure
Check condensate pan.
Check drainage by
pouring water.
Measure resistance
with a tester.
Measure resistance
with a tester.
Measure voltage
between CN36/PCN6
terminals with a tester.
Check connection.
Check connection.
High
Condensate
Level
Clogging of
Drainage
Up-Slope
Condensate
Piping
Remove foreign
particles clogging
condensate pipe.
Replace float switch
if faulty.
Replace condensate
pump if faulty.
Replace and tighten
connector.
Replace and tighten
connector.
Repair connection.
Repair connection.
Check PCB in
Self-Checking Mode *1).
Replace it if faulty.
Failure of Indoor Unit PCB
Check continuity
when condensate
level is low.
Summary of Contents for IDM030B21E Series
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...