<3. Installation>
3-6
IM 11M13A01-04E
Note 5: Cable Entry
• The threaded type of cable entry is marked beside the cable entry according to the following
markings.
Threaded type
:
Marking
M20x1.5
:
M
1/2 NPT
:
N
• In case of ANSI 1/2 NPT plug, ANSI hexagonal wrench should be applied to screw in.
• The cable entry devices (cable glands etc.) and blind plugs shall be in type of protection Ex “db” or
Ex “tb”, suitable for the conditions of use and correctly installed. They shall provide a degree of
ingress protection of at least IP66.
Note 6: Special conditions for safe use
Electrostatic charge may cause an explosion hazard. Avoid any actions that cause the generation of
electrostatic charge, such as rubbing with a dry cloth.
If it is mounted in the area where the use of Ex “tb” apparatus is required, it shall be installed in such
a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid
flow of dust is avoided.
Note 7: Special fastener
Hexagon socket head cap screws below are special fastener according to IEC 60079-0: 2011 (see
the figure below). Material property classes of them are A2-50 or better.
Special fastener
Figure 3.4
Special fastener