![YOKOGAWA vigilantplant ProSafe-RS User Manual Download Page 97](http://html1.mh-extra.com/html/yokogawa/vigilantplant-prosafe-rs/vigilantplant-prosafe-rs_user-manual_3466846097.webp)
SEE
ALSO
For more information about SYS_DIAG function block, refer to:
C10.6, “SYS_DIAG (diagnostic information output)” in Safety Control Station Reference (IM
32Q03B10-31E)
n
Setting the Domain Number
A domain stands for a range of stations in a network connected by control bus. Set the do-
main number in the range of 1 to 31. To set a domain number, set the DIP switches as fol-
lows.
•
Setting DIP switches
0: In the state shown in the following figure, the switch is tilted toward the left.
1: In the state shown in the following figure, the switch is tilted toward the right.
Bits 2 and 3 must always be zeros (0s).
P
0
0
0
1
MSB: Most Significant Bit
LSB: Least Significant Bit
6
5
4
3
2
1
7
8
MSB
LSB
Domain number
Fixed to 0
Parity of the domain number (odd parity)
Bit number
Figure 4.2.3-5 Domain Number Setting Switches
Table 4.2.3-2 Domain Number and DIP Switch Positions
Domain num-
ber
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Bit 1
0
0
1
0
1
1
0
0
1
1
0
1
0
0
1
0
Bit 2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit 3
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit 4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
Bit 5
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
Bit 6
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
Bit 7
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
Bit 8
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
Table 4.2.3-3 Domain Number and DIP Switch Positions
Domain num-
ber
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Bit 1
1
1
0
1
0
0
1
1
0
0
1
0
1
1
0
Bit 2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit 3
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit 4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Continues on the next page
<4.2 Processor Module >
4-10
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00