![YOKOGAWA vigilantplant ProSafe-RS User Manual Download Page 203](http://html1.mh-extra.com/html/yokogawa/vigilantplant-prosafe-rs/vigilantplant-prosafe-rs_user-manual_3466846203.webp)
n
Procedure for Installing Optical ESB Bus Repeater Slave Module
IMPORTANT
Use a phillips screwdriver to tighten the screws for fixing the optical ESB bus repeater slave
module. As a guideline, the screw tightening torque should be approximately 0.5 N•m.
Install the optical ESB bus repeater slave module following the steps of the "Procedure for
Removing Optical ESB Bus Repeater Slave Module" in the reverse order.
1. Screw the cable connector to the optical ESB bus repeater slave module.
2. Use the screws at the upper and lower part of the connector to fasten the cable connec-
tor.
The torque to fasten the screws on ESB bus connector is about 0.3 N•m.
3. Install the optical ESB bus repeater slave module into the base unit.
4. Use the two screws at the upper and lower part of the connector to fasten the optical ESB
bus repeater master module.
5. Uncap the fiber-optic cable and connect it to the optical ESB bus repeater slave module.
The fiber-optic cable has an IN end and an OUT end. Be sure you connect the correct
end.
6. Check the diagnostic information window on the SENG for any errors.
<7.2 Replacing Common Modules >
7-17
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00