![YOKOGAWA vigilantplant ProSafe-RS User Manual Download Page 144](http://html1.mh-extra.com/html/yokogawa/vigilantplant-prosafe-rs/vigilantplant-prosafe-rs_user-manual_3466846144.webp)
l
When Connecting SDV531 (24 V DC Power Supply Required)
1A
2A
3A
4A
5A
6A
7A
8A
9A
10A 11A 12A 13A 14A 15A 16A 17A
+
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 N.C.
COM 24 VDC
COM1 COM2 COM3 COM4 COM5 COM6 COM7 COM8 N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
COM
1B
2B
3B
4B
5B
6B
7B
8B
9B
10B 11B 12B 13B 14B 15B 16B 17B
-
N.C.
Signal Name
Signal Name
TM1, TM2
Terminal No.
N.C. : No Connection
Figure 5.4.4-7 SDV531 Signal Name and Terminal Number
l
When Connecting SDV541 (24 V DC Power Supply Required)
1A
2A
3A
4A
5A
6A
7A
8A
9A
10A 11A 12A 13A 14A 15A 16A 17A
+
OUT10 OUT11 OUT12 OUT13 OUT14 OUT15 OUT16
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9
COM 24 VDC
COM1 COM2 COM3 COM4 COM5 COM6 COM7 COM8 COM9 COM10 COM11 COM12 COM13 COM14 COM15 COM16
COM
1B
2B
3B
4B
5B
6B
7B
8B
9B
10B 11B 12B 13B 14B 15B 16B 17B
-
N.C.
Signal Name
Signal Name
TM1, TM2
Terminal No.
N.C. : No Connection
Figure 5.4.4-8 SDV541 Signal Name and Terminal Number
n
Connection Between SWD2D and an Output Module
TM4
TM3
1B
2B
3B
4B
NC
NC
ALM
NC
1A
2A
3A
4A
NC
NC
ALM
NC
R2
1B
2B
3B
4B
NC
NC
ALM
NC
1A
2A
3A
4A
NC
NC
ALM
NC
R1
TM2
TM1
1B
2B
3B
4B
NC
NC
ALM
NC
1A
2A
3A
4A
NC
NC
ALM
NC
L2
1B
2B
3B
4B
NC
NC
ALM
NC
1A
2A
3A
4A
NC
NC
ALM
NC
L1
CN1
CN2
CN3
CN4
CN5
CN6
CN7
CN8
POWER
1A
2A
3A
4A
1B
2B
3B
4B
FUSE
250V 1A
FUSE
250V 3.2A
L1
POWER
1A
2A
3A
4A
1B
2B
3B
4B
FUSE
250V 1A
FUSE
250V 3.2A
L2
POWER
1A
2A
3A
4A
1B
2B
3B
4B
FUSE
250V 1A
FUSE
250V 3.2A
R1
POWER
1A
2A
3A
4A
1B
2B
3B
4B
FUSE
250V 1A
FUSE
250V 3.2A
R2
Connect to both the CN1 and CN2, the CN3 and CN4,
the CN5 and CN6, or the CN7 and CN8 connectors
if the I/O modules are used in a dual-redundant configuration.
Fuses (1A 32 Pieces)
Fuses (3.2A 8 Pieces)
Figure 5.4.4-9 SWD2D Terminal Board
l
When Connecting SDV526 (100-120 V AC Power Supply Required)
1A
2A
3A
4A
OUT1 OUT2 OUT3 OUT4
N.C.
L
N.C.
ALM
N.C.
COM1 COM2 COM3 COM4
N.C.
N
N.C.
ALM
N.C.
1B
Signal Name
Single Name
TM1, TM2, TM3, TM4
Terminal No.
2B
3B
4B
N.C. : No Connection
Figure 5.4.4-10 SDV526 Signal Name and Terminal Number
l
Signals of SWD2D
•
External power supply voltage/current (between L and N)
4 points; 100-120 V AC, 50/60Hz; 8.8 A (2.2 A per point)
•
Output voltage/current (between OUTn and COMn) (*1)(*2)
4 points x 4 (total 16 points); 100-120 V AC, 50/60Hz; 8 A (0.5 A per point)
<5.4 Signal Cable Connection to Digital Input/Output Modules >
5-30
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00