![YOKOGAWA vigilantplant ProSafe-RS User Manual Download Page 7](http://html1.mh-extra.com/html/yokogawa/vigilantplant-prosafe-rs/vigilantplant-prosafe-rs_user-manual_3466846007.webp)
Conformity Standards and Cautions
n
Conformity Standards
The Product conforms to various standards.
SEE
ALSO
For more information about the standards that the Product conforms to, refer to:
General Specifications (GS) for the Product
l
Standards
The standards that the Product conforms to are described in the following table:
Table Info-2 Standards
Category
Standard
Functional safety standards
(*1) (*2)
IEC 61508
Programmable controllers (*1)
(*2)
IEC 61131-2
Safety Standards (*2) (*3) (*4)
[CSA]
• CAN/CSA-C22.2 No.61010-1 [100-120 V AC power supply]
[CE Marking] Low Voltage Directive
• EN 61010-1, EN 61010-2-030 [100-120 V AC (*5), 220-240 V AC, and
24 V DC power supply]
[EAC Marking] (*6)
• CU TR 004
EMC Standards (*2)
[CE Marking] EMC Directive
• EN 55011 Class A Group 1[100-120 V AC (*5), 220-240 V AC, and 24 V
DC power supply] (*7)
• EN 61000-6-2[100-120 V AC (*5), 220-240 V AC, and 24 V DC power
supply] (*8)
• EN 61000-3-2 [220-240 V AC power supply] (*9)
• EN 61000-3-3 [220-240 V AC power supply]
[RCM]
• EN 55011 Class A Group 1 [220-240 V AC and 24 V DC power supply]
(*7)
[KC Marking]
• Korea Electromagnetic Conformity Standard [100-120 V AC (*10),
220-240 V AC, and 24 V DC power supply]
[EAC Marking] (*6)
• CU TR 020
*1:
Safety control stations comply with this standard.
*2:
The devices must be installed in a metal cabinet with lock and key to meet the safety standards and EMC Standards.
*3:
To ensure that all the hardware devices satisfy the safety standards, the dedicated breakers conforming to the following spec-
ifications must be installed in the power supply distribution board:
• [CSA] CSA C22.2 No.5 or UL 489
• [CE Marking] EN 60947-1 and EN 60947-3
*4:
The Product must be grounded to a protective grounding system that is suitable for the power distribution system or must
conform to the safety standards of the country or region where the Product is used.
*5:
SSC10S/SSC10D (100-120 V AC power supply) are excluded from CE Marking conformity.
*6:
The EAC mark is as follows:
*7:
Class A hardware devices are designed for use in an industrial environment.
*8:
Regarding surge immunity, a lightning arrester or an equivalent equipment must be installed.
*9:
Regarding the requirements on the limits for harmonic current emissions, the active filter circuitry or an external power supply
unit with proper harmonic filters should be used.
*10: SSC10S/SSC10D (100-120 V AC power supply) are excluded from KC Marking conformity.
In relation to the CE Marking, the manufacturer and the authorised representative for Pro-
Safe-RS in the EEA are indicated below:
•
Manufacturer:
vi
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00