![YOKOGAWA vigilantplant ProSafe-RS User Manual Download Page 184](http://html1.mh-extra.com/html/yokogawa/vigilantplant-prosafe-rs/vigilantplant-prosafe-rs_user-manual_3466846184.webp)
6.8
Installing the Vnet/IP Interface Card in a
PC
The VI702 is installed in a slot of a PC (PC/AT compatible).
This section explains how to install the VI702 in a PC.
IMPORTANT
•
Do not turn on the power of the PC until the cables for Vnet/IP are connected.
•
Turn off the power of the PC before disconnecting the cables for Vnet/IP.
•
For a ProSafe-RS system that is not integrated with other systems, before installing the
VI702 to the PC, all internal settings in the VI702 should be erased in accordance with
the procedure for erasing VI702 internal settings.
For a ProSafe-RS system that is integrated with CENTUM system, there is no need to
erase the internal settings of the VI702.
SEE
ALSO
For more information about how to treat PCs when installing VI702, refer to:
The instruction manuals of the target PCs
n
Installation Procedure
TIP
For ProSafe-RS systems that are not integrated with other systems, follow the procedure for erasing VI702
card internal settings, and then start the installation according to the following procedure.
1. Turn off the power of the PC. For safety, remove the power plug from the outlet.
2. Correctly set the DIP switches for the domain number, station number, and Action Mode
(DIP SW4).
3. Remove the cover of the PC.
4. Insert the VI702 in the corresponding slot and fix the card.
5. Put back the cover of the PC.
6. Connect the cables to both ports of BUS1 and BUS2. There is no need to turn off the
power of the Layer2 Switch.
7. Put back the power cord of the PC.
8. Turn on the power of the PC.
9. Make sure that the RDY lamp on VI702 is ON.
10. Write the station address to the sticker that comes with the VI702 and stick it on the front
or another easy-to-see location of the PC.
l
Procedure for Erasing VI702 Internal Settings
If you intend to use a VI702 card used in another system for a system configured with Pro-
Safe-RS only, delete the settings within the card using the following procedure.
1. Turn off the power of the computer. For safety, remove the power plug from the outlet.
2. Set the DIP switches (SW1) for the domain number on the VI702 as follows:
<6.8 Installing the Vnet/IP Interface Card in a PC>
6-16
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00