L1
L2
d2
d1
L1
d2
d1
Sleeve with insulating cover
Sleeve (without insulating cover)
IMPORTANT
•
Use pressure clamp terminal sleeves and tools from the same manufacturer.
•
Use pressure clamp terminal sleeve tools suitable for the thickness of the wires.
•
Plug the cables to be connected deep into the pressure clamp terminals and make sure
they are securely installed.
•
It is recommended to use a driver that conforms to the DIN 5264B standard. The stand-
ard requires a screwdriver with a thickness of 0.6 mm at the tip and a body shaft diameter
of 3.5 mm for the cable connection.
•
The tightening torque is 0.5 N•m
•
Fasten the cables securely to cable clamps, etc., so that the cables do not weigh on the
terminals.
<5.2 How to Connect Signal Cables >
5-7
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00