7.1.2
Inspection by SCS State Management Window
The SCS state management window can be opened from the SCS Maintenance Support Tool
on SENG. On the SCS state management window, the safety control unit status, I/O module
status and control bus status can be inspected.
It is recommended to periodically check the running states of the SCS components and I/O
modules other than checking the running states only when trouble occurs.
The following figure shows the SCS state management window.
SCS State Management -[SCS0101]
File View Window Operation Tool
MYRSPJT
Domain:01
V net 1
V net 2
SCS0101
CPU Node(1)
IOM
–
–
–
SDV531(1)
SDV144(3)
SDV144(4)
SAI143(5)
SAV144(6)
SDV531(7)
CPU
PSU(L)
PSU(R)
Item
Data
Item
Data
SCS Status
CPU Status
Operating Mode
Security Level
Number of Forcing
Ready
Ready
Running
2
0
Station Name
Station Comment
Station Address
Station Type
System Revision
SCS Status
CPU Status
Flash Access
SCS0101
01-01
SSC10S-S
R3.02.00
Ready
Ready
Ready
SCS0101
SCS0101
Hardware configuration tree view
Component/module list view
Upper
Lower
Control bus status
RS project name
Figure 7.1.2-1 SCS State Management Window (In Case the V net is Connected)
SEE
ALSO
For more information about SCS state management window, refer to:
3.1.2, “Management of SCS States” in Utilities and Maintenance Reference (IM 32Q04B20-31E)
<7.1 Routine Maintenance of Safety Control Unit >
7-5
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00