The cooling fan unit is added to the standard type control unit so that the control unit works in
wider range of ambient environments (-20 to 70 deg. C).
Fan unit
Power input
terminal
Power supply unit
for fan unit
Grounding
terminal
Cable tray
Empty (1 UNIT) (*1)
Node fan unit (2 UNIT) (*1)
Utility unit (1 UNIT) (*1)
External interface unit (*1)
Base unit (5 UNIT) (*1)
*1: 1 UNIT=44.45 mm
Processor
module
Power supply module
Such as Input/Output module
Figure 1.1-6 Configuration of Safety Control Unit for Vnet/IP (SSC60D-F)
Table 1.1-6 Model Names of Safety Control Unit for Vnet/IP Components (Wide Range Temperature
Type)
Name
Wide range temperature type safety control unit
for Vnet/IP
Single configuration
(SSC60S-F)
Duplexed configuration
(SSC60D-F)
Power supply module (100-120 V AC)
SPW481
2pcs
SPW481
2pcs
Power supply module (220-240 V AC)
SPW482
2pcs
SPW482
2pcs
Power supply module (24 V DC)
SPW484
2pcs
SPW484
2pcs
Processor module
SCP461
1pcs
SCP461
2pcs
Dummy cover (for processor module) (*1)
T9083VB
1pcs
-
-
Dummy cover (for I/O module) (*2)
SDCV01
as required SDCV01
as required
ESB bus coupler module (*3)
SEC402/
SEC401
2pcs
SEC402/
SEC401
2pcs
External interface unit (for wide range temperature
type safety control unit)
-
1pcs
-
1pcs
Power supply unit for fan unit (100-120/220-240 V
AC)
S9159FA
2pcs
S9159FA
2pcs
Power supply unit for fan unit (24 V DC)
S9160FA
2pcs
S9160FA
2pcs
Fan unit
AIP602
2pcs
AIP602
2pcs
*1:
For non-redundant configuration, used to cover the slot at right-hand side of the single processor module.
*2:
Used to cover the empty I/O module slot.
*3:
SEC402 or SEC401 is required for connecting the safety node units.
<1.1 Configuration of Safety Control Unit >
1-8
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00