![YOKOGAWA vigilantplant ProSafe-RS User Manual Download Page 120](http://html1.mh-extra.com/html/yokogawa/vigilantplant-prosafe-rs/vigilantplant-prosafe-rs_user-manual_3466846120.webp)
Peel the jacket off for this length
Cable
Core
Figure 5.2.1-2 Cable
l
Cables Used
•
600 V polyvinyl chloride insulated wires (IV): JIS C 3307/IEC 60227-3
•
Polyvinyl chloride insulated wires for electrical apparatus (KIV): JIS C 3316/IEC 60227-3
•
600 V grade heat-resistant polyvinyl chloride insulated wires (HIV): JIS C 3317/IEC
60227-3
•
Heat-proof vinyl insulated wires VW-1 (UL1015/UL1007)
•
Control cables (vinyl insulated vinyl sheath cable) (CVV): JIS C 3401
l
Recommended Cable Thickness
•
Without sleeve : 0.5 mm
2
to 2 mm
2
(AWG20 to 14)
•
With sleeve : 0.5 mm
2
to 1.5 mm
2
(AWG20 to 16)
l
Wiring to Pressure Clamp Terminals (without Sleeves)
Table 5.2.1-2 Wiring to Pressure Clamp Terminals without Sleeves
Cable thickness (mm
2
)
Peel-off length (mm)
0.5 to 2 (AWG20 to 14)
11
l
Wiring to Pressure Clamp Terminals (with Sleeves)
Table 5.2.1-3 Wiring to Pressure Clamp Terminals with Sleeves
Cable
thickness
(mm
2
)
When using a sleeve with insulating cover
When using a sleeve (without insulating
cover)
Peel-off
length
(mm)
Sleeve dimension (mm)
Weidmul-
ler model
Peel-off
length
(mm)
Sleeve dimension
(mm)
Weidmul-
ler model
L1
L2
d1
d2
L1
d1
d2
0.5
11
16
10
1.0
2.6
H0.5/16
11
10
1.0
2.1
H0.5/10
0.75
11
16
10
1.2
2.8
H0.75/16 11
10
1.2
2.3
H0.75/10
1.0
11
16
10
1.4
3.0
H1/16
11
10
1.4
2.5
H1/10
1.25 to
1.5
11
16
10
1.7
3.5
H1.5/16
11
10
1.7
2.8
H1.5/10
<5.2 How to Connect Signal Cables >
5-6
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00