3.1
Power Cable Wiring
This section explains how to connect the power supply cable to the cabinet.
n
Power Cable Wiring
CAUTION
•
The power cable must be wired through a conduit at the entrance of the cabinet for the
following reasons:
•
To prevent the power cable from being damaged through direct contact with the met-
al plate.
•
To prevent an excessive load being applied to the power supply connection terminals
due to the weight of the cable itself.
•
Turn off the power supply source, and be sure that no electricity is flowing into the power
cable to be connected before starting the work.
•
After the power cable has been connected, turn on the power to the power cable with the
breaker in the power panel turned OFF. Then, confirm with a tester that normal power is
being supplied to the power input terminal.
•
Wire the power cable by keeping a minimum distance of 1 cm from other signal wiring.
SEE
ALSO
For more information about power cable wiring and grounding, refer to:
ProSafe-RS Installation Guidance (TI 32S01J10-01E)
n
Connecting Power Cables to Each Device
Power supply cables for each device are to be prepared by the user.
l
Connecting Power Cables to the Power Supply Module and the Power Unit
for the Fan
Connect the power supply using the following sequence of steps.
1. Attach the Plugs for M4 screws to the end of the cables.
2. Remove the protective cover of the power supply module.
3. For AC power supply, connect the non-grounding side to the terminal L and the grounding
side to the terminal N.
For 24V DC power supply, connect the non-grounding side to the terminal (+) and the
grounding side to the terminal (-).
4. Replace the protective cover.
l
Connecting the Power Cable to the Power Distribution Unit
Yokogawa also provides the following power distribution units and power cables as one of the
choices.
•
Power distribution unit
AEPV7D-111: 100-120 V AC
AEPV7D-211: 220-240 V AC
<3.1 Power Cable Wiring >
3-2
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00