MIL connector
Pressure clamp
terminal block
I/O modules
Connector cover
Mounting Screws
Figure 7.3.2-2 Removing Terminal Blocks
l
Removal Procedure
1. Remove the fixing screws. There are two screws in the case of a terminal block or a MIL
connector cover.
2. Pull the terminal block forward and remove it from the I/O module.
l
Installation Procedure
1. Install the terminal block following the steps of the "Removal Procedure" in the reverse
order.
2. The tightening torque of the fixing screws should be approximately 0.5 N•m.
n
Replacing Input/Output Modules in Dual-Redundant Connection
I/O modules in dual-redundant connection must be connected to consecutive slots beginning
from an odd number.
l
Removal and Installation Procedure
1. Check the LED displays of the pair of I/O modules in dual-redundant connection to see
that the STATUS and DX LEDs are lit for both modules and ACT is lit for only one of
them.
2. Remove the four screws at the upper and lower parts of the terminal block.
3. Remove the terminal block while supporting it so as not to apply too much stress to the
flat cable.
4. While supporting the terminal block, remove the connector connected to the I/O module
whose ACT LED is not lit.
5. Remove the two screws of the I/O module whose ACT LED is not lit, and replace it with
an adjusted I/O module. Fix the screws of the replaced I/O module.
6. Download the setting information to the replaced I/O module. In SCS Constants Builder,
if Automatic IOM Download is set to [Enable], the IOM download will be performed auto-
matically.(*1)
7. Reinstall the flat cable connector.
<7.3 Replacing Input/Output Modules >
7-24
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00