For more information about settings on I/O Parameter Builder, refer to:
A4.6, “Items set for discrete inputs” in Safety Control Station Reference (IM 32Q03B10-31E)
n
Connecting the SBM54D to a Digital I/O Module
The following table shows the relations of the digital I/O modules connector numbers and the
connected field terminal numbers.
Table 8.3.1-7 Connector Numbers and Connected Field Terminal Numbers
Connector num-
ber
Connection
Field terminal number
Remarks
CN1
SDV541
1 to 16
CN1/CN2 redundancy
CN2
The following table shows the relations among the relay numbers, the field terminals, the digi-
tal output module connectors, and the SDV541/SDV144 channel numbers.
Table 8.3.1-8 Relay Numbers/Field Terminals/Channel Numbers
Relay number
(*1)
Field terminal
CN1
CN2
SDV541 channel number
SDV541
1
1A/1B
ch1
ch1
2
2A/2B
ch2
ch2
3
3A/3B
ch3
ch3
4
4A/4B
ch4
ch4
5
5A/5B
ch5
ch5
6
6A/6B
ch6
ch6
7
7A/7B
ch7
ch7
8
8A/8B
ch8
ch8
9
9A/9B
ch9
ch9
10
10A/10B
ch10
ch10
11
11A/11B
ch11
ch11
12
12A/12B
ch12
ch12
13
13A/13B
ch13
ch13
14
14A/14B
ch14
ch14
15
15A/15B
ch15
ch15
16
16A/16B
ch16
ch16
*1:
The relay number is the number printed on the SRM54D metal body above each relay.
IMPORTANT
When SDV541 is connected to SBM54D, Detect Disconnection, Pulse Test (OFF) and Pulse
Test (ON) should be disabled on I/O Parameter Builder.
SEE
ALSO
For more information about settings on I/O Parameter Builder, refer to:
A4.7, “Items set for discrete outputs” in Safety Control Station Reference (IM 32Q03B10-31E)
<8.3 Cable Connection >
8-9
IM 32Q06C10-31E