![YOKOGAWA vigilantplant ProSafe-RS User Manual Download Page 24](http://html1.mh-extra.com/html/yokogawa/vigilantplant-prosafe-rs/vigilantplant-prosafe-rs_user-manual_3466846024.webp)
*1:
For non-redundant configuration, used to cover the slot at right-hand side of the single processor module.
*2:
Used to cover the empty I/O module slot.
*3:
Required if the safety nodes are used.
n
Wide Range Temperature Type Safety Control Unit for V net
The components of the wide range temperature type safety control unit (Model: SSC10S-F/
SSC10D-F) are shown in the following figure.
This type of control unit consists of the standard type control unit and cooling fan unit so as to
work in a wider range of ambient environment (-20 to 70 deg. C).
4
5
6
1
2
3
RX+ RX- SG
Fan unit
Power input
terminal
Power supply unit
for fan unit
Grounding
terminal
Cable tray
V net coupler unit
*1: 1 UNIT=44.45 mm
Empty (1 UNIT) (*1)
Node fan unit (2 UNIT) (*1)
Utility unit (1 UNIT) (*1)
External interface unit
Base unit (5 UNIT) (*1)
GPS interface unit (option)
Processor
module
Power supply module
Such as Input/Output module
Figure 1.1-2 Configuration of Safety Control Unit (SSC10D-F)
Table 1.1-2 Model Names of Safety Control Unit Components (Wide Range Temperature Type)
Name
Wide range temperature type safety control unit
Single configuration
(SSC10S-F)
Duplexed configuration
(SSC10D-F)
Power supply module (100-120 V AC)
SPW481
2pcs
SPW481
2pcs
Power supply module (220-240 V AC)
SPW482
2pcs
SPW482
2pcs
Power supply module (24 V DC)
SPW484
2pcs
SPW484
2pcs
Processor module
SCP401
1pcs
SCP401
2pcs
Dummy cover (for processor module)(*1)
T9083VB
1pcs
-
-
Dummy cover (for I/O module)(*2)
SDCV01
as required SDCV01
as required
ESB bus coupler module(*3)
SEC401
2pcs
SEC401
2pcs
V net coupler unit
AIP504
2pcs
AIP504
2pcs
External interface unit (for wide range temperature
type safety control unit)
-
1pcs
-
1pcs
Power supply unit for fan unit (100-120/220-240 V
AC)
S9159FA
2pcs
S9159FA
2pcs
Power supply unit for fan unit (24 V DC)
S9160FA
2pcs
S9160FA
2pcs
Fan unit
AIP602
2pcs
AIP602
2pcs
Continues on the next page
<1.1 Configuration of Safety Control Unit >
1-4
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00