Figure 8.3.3-5 SRM54D Terminal Numbers and Signal Names
CAUTION
•
The “+” and “-” of TM3 terminals are used for connecting the power supply.
•
Before wiring is started, the protective cover for the terminals needs to be removed. And
the cover should be put back after the wiring is completed.
•
It is recommended to place mediate switches or breakers in the power supply wirings so
that the power supply of each circuit can be shutoff individually during maintenance.
n
SBM54D Terminal Numbers and Signal Names
CN1
CN2
POWER1
POWER2
FUSE1
250V T 10A
FUSE2
250V T 10A
READY
1A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
2A 3A 4A 5A 6A 7A 8A
1B 2B 3B 4B 5B 6B 7B 8B
9A 10A 11A 12A 13A 14A 15A 16A
9B 10B 11B 12B 13B 14B 15B 16B
Figure 8.3.3-6 SBM54D relay board
1A
2A
3A
4A
5A
6A
7A
8A
9A
10A
11A
12A
13A
14A
15A
16A
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15 OUT16
COM1 COM2 COM3 COM4 COM5 COM6 COM7 COM8 COM9 COM10 COM11 COM12 COM13 COM14 COM15 COM16
1B
2B
3B
4B
5B
6B
7B
8B
9B
10B
11B
12B
13B
14B
15B
16B
24V DC COM 24V DC COM
1+
1-
2+
2-
READY
READY
Signal Name
Signal Name
Terminal No.
Signal Name
Terminal No.
Signal Name
Terminal No.
Figure 8.3.3-7 SBM54D Terminal Numbers and Signal Names
CAUTION
•
You can use dual power supply. The "1+" "1-" and "2+" "2-" of TM3 terminals are used for
connecting the power supply.
•
It is recommended to place mediate switches or breakers in the power supply wirings so
that the power supply of each circuit can be shutoff individually during maintenance.
<8.3 Cable Connection >
8-13
IM 32Q06C10-31E
4th Edition : Jan.30,2015-00