<8. Detailed Data Setting>
8-14
IM 11M12D01-01E
8.5 Other Settings
8.5.1 Date and Time
Here we explain how to set date and time. Date and time setting are used for Auto Calibration and
Auto Indication Check, also Auto Blow back Start time.
<Setting Procedure>
1) From the basic panel display if you touch the Setup key, the [Execution/Setup] display appears.
2) Select [Commissioning] and the Commissioning display appears.
3) Select [Others] and the display of Figure 8.17 appears.
4) Select [Clock] and the display of Figure 8.18 appears.
5) Select [Set date] and the numerical entry display appears. To enter June 21. 2004 , enter
[210604]. Touch the Enter key and you revert to the display of Figure 8.17.
6) Select [Set time]. Enter the time in 24-hour format. To set 2:30 pm, enter [1430] on the numerical
display and touch the Enter key. The clock starts from 00 seconds.
Enter
F8-17E.zi
Clock
Averaging
Fuel setup
Purging
Unit setup
Asymmetry alarm
Passwords
Defaults
Others
Enter
F8-18E.ai
Set date: 2 1 / 0 6 / 0 4
Set time: 1 6 : 4 4
2 1 J un. 2 0 0 4
1 6 : 4 4 : 4 5
Clock
Figure 8.17 Others setting display
Figure 8.18. Day and Time setting
8.5.2 Average Value / Max. and Min. Monitoring Time
This instrument can compute and display Average, Max. and Min. Oxygen concentrations in a
specified time interval. The Average, Max. and Min. can apply to each channel and to averaging
outputs a, b and c. Here we explain how to set the time interval for averaging, and for monitoring for
Max./Min.
<Setting Procedure>
1) From the panel basic display touch Setup key, and the [Execution/Setup] display appears.
2) Select [Commissioning] and the Commissioning display appears.
3) Select [Others] then [Averaging]. The display of Figure 8.19 appears.
4) Select “Set period over which average is calculated” and numerical entry display appears. To set
3 hours, enter 003. Entry range is 1 to 255 hours.
5) Select “Set period over which maximum and minimum is stored” and numerical entry display
appears. To set 48 hours, enter 048. Entry range is 1 to 255 hours.