ADPRO FastTx by Xtralis
Installation and User Manual
Doc 11949_06
3
2 ADPRO FastTx Setup Instructions
This chapter contains instructions to setup the ADPRO FastTx.
2.1
Physical Location
The location within the protected premises of the ADPRO FastTx should be considered carefully
and the following notes are provided for guidance.
•
Physical Security
- The ADPRO FastTx should be located where it will remain secure
under all conditions, even when the premises are open or occupied. The safest place would
be a room (or cabinet) with a lockable door. It should not be visible from outside the
premises and not be accessible to occupant or visitor tampering.
Caution:
ADPRO FastTx equipment must be used only in an INDOOR environment.
•
System Wiring
- Ideally, the ADPRO FastTx’s position will be close to the centre of the site
wiring. Excessive cable runs will increase the installation cost, cause voltage drops,
degrade signals, and offer greater scope for EMI/RFI (electrical interference) induced faults,
tampers, and false alarms. Wiring considerations should include the following:
-
The largest wiring requirement is the coaxial camera cabling and the wiring to the
alarm input and output devices
-
Mains power
-
The system requires at least one video camera and associated coaxial cabling for
system setup
•
Environment
- Choose an inside location that is cool and dry. Do not mount the ADPRO
FastTx anywhere near machinery that generates heat, toxic fumes and dust. Do not mount
the ADPRO FastTx in close proximity to sources of radio frequency or other
electromagnetic radiation. These include radio transmitters (both fixed and portable),
electric motors, refrigeration or air conditioning systems and high power or multiphase
switching equipment.
2.2
General Power Requirements
Any AC supply connected to the ADPRO FastTx should be:
•
Provided from a reliable electric supply company - typically this means that the power is not
disconnected (or lost) for any more than eight hours at a time in any 36 hour period and
infrequently in a single year.
•
Provided from a supply bus within the protected premises that is not isolated at night (or out
of hours) or time switched. The supply should be free from voltage spikes or current surges
(connected to high power switching equipment or electric motors).
•
Supplied directly to the ADPRO FastTx via circuits that cannot be switched off, intentionally
or accidentally.
Always consider local regulations, standards, and guidelines for mains power connected
systems.
Caution:
The ADPRO FastTx is a Class 1 electrical product and must always be connected
to a grounded power outlet.
Always ensure that ADPRO FastTx is installed adjacent to a grounded power outlet.