Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
33
CPU OK indicator (green/red)
This bi-color LED indicates the CPU status is operational (green) or faulty (red). The CPU will flash fault
codes (red) if they exist. This LED exists on both the Front Panel and back cover.
IOLOCK indicator (red)
Indicate the controller is shutdown and held in an IOLOCK state. This LED exists on both the Front Panel
and back cover.
ALARM indicator (yellow)
Viewable from the front panel and controlled by GAP software.
TRIPPED indicator (red)
Viewable from the front panel and controlled by GAP software.
Ethernet LED's
(green=link, yellow=traffic) on each RJ45 connector indicate port status and operation.
CPU Hardware Configuration
The CPU Configuration Switch (S1) is reserved for future use and is not active at this time.
Communications (Ethernet)
There are (4) isolated RJ45 Ethernet Ports (10/100 Mbit/sec) available to the application software for
system use. These ports are full duplex with auto crossover detection.
Features
Interface
standard:
IEEE 802.3 (Ethernet)
Port Isolation: 1500 Vrms to PS, EARTH, and all other circuits
Control configuration using Woodward AppManager
Control monitoring, trending, and datalog collection
Control configuration of Ethernet IP addresses
General communications such as Modbus master/slave
Manage Configuration data and tunables with Control Assistant
Network time setup and control (SNTP)
Network Configuration
.
Ethernet ports (ETH1-4) can be configured for the customer network as desired. See the on-site Network
Administrator to define an appropriate I/P address configuration.
ETHERNET CABLES—Max cable length is 100 meters. To ensure
signal integrity and robust operation, double shielded (SSTP) Cat5
Ethernet cables are required for customer installations.
(Woodward PN 5417-394, 10 feet)
This module has been factory configured with fixed Ethernet IP
addresses of
Ethernet #1 (ETH1) = 172.16.100.15, Subnet Mask = 255.255.0.0
Ethernet #2 (ETH2) = 192.168.128.20, Subnet Mask =
255.255.255.0
Ethernet #3 (ETH3) = 192.168.129.20, Subnet Mask =
255.255.255.0
Ethernet #4 (ETH4) = 192.168.130.20, Subnet Mask =
255.255.255.0