505XT Digital Control System for Steam Turbines
Woodward
162
User Login Levels
Pressing the MODE key at any time will open the Login and Mode Screen
Figure 5-5. Mode Screen
Monitor –
(logout to enter this)
Even Keypad Green keys inhibited
Operator –
(passwords are provided in Vol 2 Appendix C)
Intended for normal turbine operation – default mode
Screen saver initiates to this level
Service –
(passwords are provided in Vol 2 Appendix C)
Allows tuning of parameters, while turbine is running (PID dynamics) and entering of Calibration Mode
Configure –
(passwords are provided in Vol 2 Appendix C)
Highest user authority / can enter any Mode
EMERGENCY STOP is always available in all modes and logins as it
has direct H/W action to open the Actuator circuits.
To Login –
1.
Press the LOGIN button
2. ** Navigate so the Login or Password field is highlighted (in-focus)
3. Press
Enter
on the Navigation Cross
4. Use the keypad to enter the text field
(hold key down to scroll options)
5. Press
Enter
on the Navigation Cross – to accept your entry
** Or you can navigate to the Autofill buttons and press Enter – it will auto-populate the Login information
so you only need to enter the Password.